USER CONFIGURABLE ITEMS
NOTE: SETTING THESE ITEMS REQUIRES SOFTWARE, OPTIONAL HARDWARE, OR
CONFIGURATION IN TERMINAL MODE.
FUNCTION | FACTORY | USER SELECTABLE | DESCRIPTION | |
DEFAULT | CHOICES | |||
|
| |||
Automatic Self- | Every 14 days | Every 7 days | This function sets the interval at which the | |
Test | (336 hours) | (168 hours), | UPS will execute a | |
|
| On Startup Only, | software manual for details. | |
|
| No |
| |
|
|
|
| |
UPS ID | UPS_IDEN | Up to eight charac- | Use this field to uniquely identify the UPS | |
|
| ters to define the | for network management purposes. | |
|
| UPS |
| |
|
|
|
| |
Date of Last Bat- | Manufacture | Date of Battery | Reset this date when you replace the battery | |
tery Replacement | Date | Replacement | pack. | |
|
|
|
| |
Minimum Capacity | 0 percent | 15, 25, 35, 50, 60, | The UPS will charge its batteries to the | |
Before Return from |
| 75, 90 percent | specified percentage before return from a | |
Shutdown |
|
| shutdown. | |
|
|
|
| |
Duration of Low | 2 minutes | 5, 7, 10, 12, 15, 18, | This function sets the time before shutdown | |
Battery Warning |
| 20 minutes | at which the UPS issues a low battery | |
|
|
| warning. Set it higher than the default if the | |
|
|
| operating system needs more time for shut- | |
|
|
| down. | |
|
|
|
| |
Alarm Delay After | 5 second delay | 30 second delay, At | Set the alarm delay to avoid alarms for | |
Line Fail |
| Low Battery Condi- | minor power glitches. | |
|
| tion, No Alarm |
| |
|
|
|
| |
Shutdown Delay | 20 seconds | 0, 60, 120, 240, 480, | This function sets the interval between | |
|
| 720, 960 seconds | when the UPS receives a shutdown com- | |
|
|
| mand and when shutdown occurs. | |
|
|
|
| |
Synchronized | 0 seconds | 20, 60, 120, 240, | The UPS will wait the specified time after | |
| 480, 720, 960 sec- | the return of utility power before | ||
|
| onds | (for example, to avoid branch circuit over- | |
|
|
| load). | |
|
|
|
| |
Output Voltage | 230 VAC | 240, 220, 225 VAC | Nominal output voltage setting. | |
Setting |
|
|
| |
|
|
|
| |
High Transfer | + 10% of output | +5%, +15%, +20% | Maximum voltage that the UPS will pass to | |
Point | voltage setting |
| the load during internal bypass operation. | |
|
|
|
| |
Low Transfer Point | Minimum voltage that the UPS will pass to | |||
| voltage setting | the load during internal bypass operation. | ||
|
|
|
|
8 |