American Power Conversion XS 1500 Troubleshooting, Service, Order Replacement Battery Cartridge

Models: XS 1500

1 2
Download 2 pages 21.99 Kb
Page 2
Image 2
TROUBLESHOOTING

TROUBLESHOOTING

SPECIFICATIONS

 

 

SPECIFICATIONS SERVICE SERVICE

If the Back-UPS arrived damaged, notify the carrier.

Problem

Possible Cause

Corrective Action

 

 

 

Back-UPS will not switch on.

Back-UPS not connected to AC power source.

Ensure the Back-UPS is securely connected to an AC outlet.

 

 

 

 

Back-UPS circuit breaker “tripped”.

Disconnect non-essential equipment from the Back-UPS. Reset

 

 

(push in) the rear panel circuit breaker. Switch on the Back-UPS

 

 

and plug in devices one at a time. If the circuit breaker trips

 

 

again, disconnect the device that caused the breaker to trip.

 

 

 

 

Utility input voltage quality is out of range.

Consider adjusting the transfer voltage and sensitivity. See

 

 

Transfer Voltage and Sensitivity Adjustment.

 

 

 

Back-UPS does not power

Equipment plugged into a Surge Only outlet.

Unplug device from 'Surge Only' outlet and move to a 'Battery

essential equipment during an

 

Backup' outlet.

outage.

 

 

 

 

 

Back-UPS operates on battery

Back-UPS circuit breaker “tripped”.

Disconnect non-essential equipment from the Back-UPS. Reset

although utility power exists.

 

(push in) the rear panel circuit breaker. Switch the Back-UPS on

 

 

and plug equipment in one-at-a-time. If the circuit breaker trips

 

 

again, disconnect the device that caused the breaker to trip.

 

 

 

 

Utility input voltage quality is out of range.

Consider adjusting the transfer voltage and sensitivity. See

 

 

Transfer Voltage and Sensitivity Adjustment.

 

 

 

Back-UPS does not provide

Back-UPS is heavily loaded.

Unplug non-essential equipment (printers, scanners, etc) from

expected backup time.

 

the Battery Backup outlets and plug into 'Surge Only' outlets.

 

 

 

 

Back-UPS battery cartridge is discharged due to

Charge the battery cartridge for 8 hours. Back-UPS runtime is

 

recent power outage and has not had time to

reduced until the battery cartridge is fully charged.

 

recharge.

 

 

 

 

 

Battery has reached the end of its life.

Replace battery cartridge (see Order Replacement Battery

 

 

Cartridge).

 

 

 

Red Replace Battery indicator is

Internal battery cartridge is not connected.

Connect battery cartridge (see Connect Battery Cartridge).

flashing. Green On Line indicator

 

 

is on.

 

 

 

 

 

Red Replace Battery indicator is

Battery has reached the end of its life.

Replace the battery cartridge (see Order Replacement Battery

on.

 

Cartridge).

 

 

 

Red Overload indicator is on or

Connected equipment is drawing more power than

Move one or more equipment power plugs from Battery Backup

flashing.

the Back-UPS can provide.

outlets to Surge Only outlets.

 

 

 

Green On Line indicator is on and

Internal UPS fault.

Contact APC Technical Support (see Contact Information).

all other front panel indicators are

 

 

flashing.

 

 

 

 

 

ORDER REPLACEMENT BATTERY CARTRIDGE

The battery cartridge in the Back-UPS typically lasts 3-6 years, shorter if subjected to frequent outages or elevated temperatures. Note: Batteries in the battery pack are not user-replaceable. The battery cartridge and battery pack can be ordered online at www.apc.com. For the Back-UPS, order part number RBC33; for the battery pack order BR24BP. Please recycle spent battery cartridges.

REPLACE BATTERY CARTRIDGE

Battery

Cartridge

Item

Specification

 

 

On-line Input Voltage Range

88 - 139 Vac

(default setting)

 

 

 

Automatic Voltage Regulation (AVR)

+12%

 

 

On-line Frequency Range

47 - 63 Hz (autosensing)

 

 

On-battery Waveshape

Stepped Sine Wave

 

 

Maximum Load

1500 VA - 865 W

 

 

Typical Recharge Time

24 Hours

 

 

Operating Temperature

32o to 104oF

 

0o to 40oC

Storage Temperature

23o to 113oF

 

-5oto 45oC

Operating / Storage Relative Humidity

0 to 95% non-condensing

 

 

Size (H x W x D)

14.6 x 6.8 x 13.1 inch

 

37.1 x 17.2 x 33.3 cm

 

 

Weight

52.5 lbs (23.5 kg)

 

 

Shipping Weight

58.5 lbs (26.5 kg)

 

 

EMI Classification

FCC / DOC Class B Certified

 

 

On Battery Run-Time

See http://www.apc.com/product

 

 

TRANSFER VOLTAGE AND SENSITIVITY ADJUSTMENT

In situations where the Back-UPS or connected equipment appears too sensitive to input voltage, it may be necessary to adjust the transfer voltage. This is a simple task requiring use of the front panel pushbutton. To adjust the transfer voltage, proceed as follows:

1.Plug the Back-UPS into the utility power source. The Back-UPS will be in a Standby Mode (no indicators lit).

2.Press the front panel pushbutton fully inward for 10 seconds. All indicators on the Back-UPS will flash to acknowledge going into Programming Mode.

3.The Back-UPS will then indicate its current Lower Transfer Voltage, as shown in the following table.

Indicators Lit

Lower Transfer Voltage

Use When

 

Sensitivity

 

 

 

 

1

78 Vac

Use only for extreme conditions of low

 

Low

input voltage. Not recommended for

 

 

computer loads.

 

 

 

2

83 Vac

Back-UPS frequently goes On Battery

 

Medium

due to low input voltage.

 

 

 

3

88 Vac

Connected equipment is sensitive to

 

High

low voltage (recommended).

 

(factory default)

 

 

 

 

4.To select 78 volts as the Lower Transfer Voltage, press the pushbutton until 1 indicator is flashing.

5.To select 83 volts as the Lower Transfer Voltage, press the pushbutton until 2 indicators are flashing.

6.To select 88 volts as the Lower Transfer Voltage, press the pushbutton until 3 indicators are flashing.

7.Once in Programming Mode, if the pushbutton is not pressed within 5 seconds, the Back-UPS will exit Programming Mode; all indicators will extinguish.

If the Back-UPS requires service, do not return it to the dealer. The following steps should be taken:

1.Consult the Troubleshooting section to eliminate common problems.

2.If the problem persists, go to http://www.apc.com/support/.

3.If the problem still persists, contact APC Technical Support.

Have the Back-UPS model number, serial number and date of purchase available. Be prepared to troubleshoot the problem with an APC Technical Support representative. If this is not successful, APC will issue a Return Merchandise Authorization (RMA) number and a shipping address.

LIMITED WARRANTY

The standard warranty is two (2) years from the date of purchase. APC’s standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact with an APC Technical Support representative. APC will ship the replacement unit once the defective unit has been received by the repair department, or cross-ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to APC. APC pays ground freight transportation costs to ship the replacement unit to the customer.

CONTACT INFORMATION

Technical Support

http://www.apc.com/support

Internet

http://www.apc.com

USA / Canada

1.800.800.4272

Mexico

292.0253 / 292.0255

Brazil

0800.12.72.1

Worldwide

+1.401.789.5735

990-2121 1/03 Copyright © 2003 American Power Conversion All rights reserved. APC, PowerChute plus Personal Edition, and Back-UPS are registered trademarks of American Power Conversion.

All other trademarks are the property of their respective owners.

Page 2
Image 2
American Power Conversion XS 1500 Troubleshooting, Service, Order Replacement Battery Cartridge, Limited Warranty, Problem