Installation

Caution

Equipment Damage!

Before hanging the unit on suspension rods, reinforce the cabinet around the knockouts by using a large washer inside the cabinet. Washers should be between the skin of the air handler and the nut on the suspension rod.

Align holes (knockouts) in the cabinet with structural supports and secure suspension rods to the structure, then to the air handler cabinet. If knockout locations do not permit proper alignment with existing structure, it may be necessary to field fabricate cross members on existing structural beams.

Note: When other than bottom return is to be used, side panel removed for return duct installation must be secured over the bottom opening.

Leveling

This air handler has a double sloped drain pan. In order to assure proper drainage along the length of the drain pan, it is important to have the unit properly leveled. Be sure the air handler is level or slightly sloped in the direction of the condensate connection.

Auxiliary Drain Pan

A field fabricated, auxiliary drain pan should be installed under the unit for all horizontal applications and when air handlers are installed above ceilings or in other locations where condensate overflow may cause damage. This drain pan will eliminate any excess condensation that may be due to extreme humidity or an obstructed drain in the primary drain pan. Drain lines from this pan must

be installed, but should not be connected to the primary drain line from the unit. Isolate the auxiliary drain pan from both the air handler and the structure.

￿WARNING

Fiberglass Wool!

Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers may also cause respiratory, skin or eye irritation.

Precautionary Measures

Avoid breathing fiberglass dust.

Use a NIOSH approved dust/mist respirator.

Avoid contact with the skin or eyes. Wear long-sleeved, loose- fitting clothing, gloves, and eye protection.

Wash clothes separately from other clothing: rinse washer thoroughly.

Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respirator in these situations.

First Aid Measures

Eye Contact - Flush eyes with water to remove dust. If symptoms persist, seek medical attention.

Skin Contact - Wash affected areas gently with soap and warm water after handling.

Refrigerant Piping

Installation, brazing, leak testing and evacuation of refrigerant lines are covered in the installation instructions packaged with the outdoor unit. Read the instructions before beginning installation of refrigerant lines.

Locate cloth bag(s) attached to the refrigerant tube of the coil that

contains two (2) brass clamps (straps) and cork impregnated insulation material approximately 9" long by 4" wide. This is for attaching and insulating the expansion valve bulb(s) to the suction line(s).

On air handlers that will have refrigerant lines entering the cabinet from the left side, remove the split rubber grommet from the knockout in the end of the air handler. Uncoil the cap tub with the bulb attached at the expansion valve and place the grommet on the cap tube. With the grommet around the tube, push the bulb through the hole and position the grommet back into its original position (one bulb and cap tube on single circuit units and two bulbs and cap tubes on dual circuit units).

Attach the bulb(s) approximately 45° off vertical, 10 to 12 inches outside of the air handler.

On air handlers that will have refrigerant lines entering the cabinet from the right side, the bulb(s) should be attached to the suction tube(s) inside the cabinet in the same manner as above, approximately 10" from the right end of the unit.

After attaching to the suction line(s), either inside or outside of the cabinet, wrap the cork impregnated insulation around the bulb(s) and suction tube(s). Refrigerant piping should be insulated.

Note: Important! Ensure that the refrigerant lines passing through the cabinet are not resting on sharp sheet metal edges.

Condensate Piping

The drain pan condensate connection is a female slip joint type for 1" Schedule 40 PVC pipe. Use PVC cement and tubing as required (field supplied) to construct a trap. A union or flexible tubing and clamps may be installed if the drain pan is to be removed periodically for cleaning.

12

TWE-SVX03C-EN

Page 12
Image 12
American Standard TWE120B***E Leveling, Auxiliary Drain Pan, Precautionary Measures, First Aid Measures, Condensate Piping

TWE060B***E, TWE060A***E, TWE050AD**E, TWE200BD**F, TWE120A***F specifications

The American Standard TWE series of air handlers, including models TWE180B***E, TWE075AD**E, TWE100BD**E, and TWE240B***F, represent a blend of robust engineering, energy efficiency, and advanced technology designed to meet a variety of climate control needs in residential and light commercial settings.

One of the standout features of these air handlers is their adaptability to both cooling and heating functions, particularly the heat pump configurations. This dual functionality makes them ideal for regions with fluctuating temperatures, providing comfortable indoor environments year-round. The TWE series can efficiently maintain desired temperatures, whether in cooling mode during hot summers or heating mode in colder months.

Energy efficiency is a hallmark of the TWE models. Many of these air handlers are equipped with high SEER (Seasonal Energy Efficiency Ratio) and HSPF (Heating Seasonal Performance Factor) ratings, ensuring that energy consumption is kept to a minimum. This not only contributes to lower utility bills but also aligns with contemporary environmental standards.

The TWE240B***F model exemplifies American Standard's commitment to quiet operation. Noise reduction features, such as insulated cabinets and optimized fan designs, ensure that the unit operates quietly, making it suitable for residential areas where noise can be a concern.

Durability and reliability are key characteristics of the TWE series. Constructed with high-quality materials, these air handlers are designed to withstand the rigors of varying weather conditions. Many units also come with extensive warranties, underscoring the confidence in their longevity and performance.

Installation flexibility is another advantage of the TWE series. These air handlers can be configured for horizontal or vertical applications, allowing for versatile installation options in different home layouts.

The TWE models are also compatible with advanced thermostats and zoning systems, enabling homeowners to optimize comfort and efficiency based on their specific needs. Smart technology integration further enhances control over indoor climates, ensuring that users can manage their environment conveniently.

In summary, the American Standard TWE series air handlers—TWE180B***E, TWE075AD**E, TWE100BD**E, and TWE240B***F—combine energy efficiency, versatility, quiet operation, and long-lasting durability. These features make them an excellent choice for those seeking reliable cooling and heating solutions in their homes or small commercial spaces.