AMX RDA-ENC12B installation instructions Installation Guide, Installation Instructions, Side View

Models: ENC12B RDA-ENC12B RDA-ENC6B

1 2
Download 2 pages 28.39 Kb
Page 1
Image 1
Installation Guide

Installation Guide

RDA-ENC6B and ENC12B Dimmer Enclosures w/Breakers

The RDA-ENC6B (FG606-13) and RDA-ENC12B (FG606-14) enclosures provide secure mounting for all AMX Lighting and ProLink controllers, and lighting modules. These enclosures contain circuit breakers.

TOP VIEW

 

 

 

0.75"

 

 

 

 

 

 

(19.05 mm)

 

 

 

 

 

 

 

 

 

6.0"

(152.4 mm)

These enclosures are CE, UL, and C-UL approved. They include circuit breakers and terminals for multi-phase wiring.

They also provide 18 knockouts for 1/2", 3/4", and 1" conduits.

RDA-ENC6B Configurations:

-ENC6B/120 20 A Breakers

-ENC6B/240 10 A Breakers

 

 

RDA-ENC12B Configurations:

SIDE VIEW

 

- ENC12B/120 20 A Breakers

 

- ENC12B/240 10 A Breakers

 

 

 

 

 

 

 

 

 

 

 

 

RDK Configurations:

 

 

 

 

 

 

 

 

 

 

- RDK-ENC6B with 1 RDC-PDC

 

 

 

 

 

 

 

 

 

 

- RDK-ENC12B/240 2 RDC-PDC

 

 

 

 

 

 

 

 

 

 

 

24.0"

 

 

24.0"

 

 

(610 mm)

(610 mm)

 

 

 

RDA-ENC6B

 

 

 

 

 

 

 

RDA-ENC12B

Sample RDK-ENC12B kit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

shown with 2 RDC-PDC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18.0" (457.2 mm)

Top, side, and bottom views are the same for both enclosures.

BOTTOM VIEW

Note:

LINE INPUTS: 120 A MAX PER TERMINAL Use 75° C copper conductors only.

Torque terminals to 44 in-lbs.

FIG. 1 Top, front, bottom, and side views of the RDA-ENC6B and RDA-ENC12B enclosures

Installation Instructions:

For indoor use only.

Mount on vertical surface only.

Maintain 12" (304.88 mm) minimum clearance above and below the enclo- sure.

Route class 1 conductors through upper conduit knockouts.

Route class 2 conductors through lower conduit knockouts.

Use 75°C (167°F) copper conductors only.

Install filler plate #28-10500 (RDA-EFP) in all unused openings.

Install only UL approved modules (see the UL Number Cross Reference to AMX Lighting ID table on page 2).

Enclosure Weights:

RDA-ENC6B: 16.5 lbs. (7.48 kg)

RDA-ENC12B: 17.5 lbs. (7.94 kg)

Dimensions between center lines (from FIG. 2):

RDA-ENC6B:

A to B = 16.0" (406.4 mm)

B to C = 22.88" (581.2 mm)

RDA-ENC12B:

A to B = 16.0" (406.4 mm)

B to C = 22.88" (581.2 mm)

Radia enclosures must be mounted on a vertical surface with a minimum of 12" (304.8 mm) clearance above and below the enclosure.

Configuration for

 

right and left

A to B

mounting brackets

 

for all Radia

Top slot

enclosures.

 

 

B to C

Maximum mounting

 

screw size: #12

 

 

Bottom slot

FIG. 2 Bracket configuration

Specifications

Maximum input wire #1/0 AWG (50mm²)

Maximum line input is 120 A (per terminal)

Torque input wire to 44 in-lbs. (5.0 N/m)

Wire stripping length: 0.67 inches (17 mm)

Input 1 feeds channels 1, 4, 7, and 10

Input 2a feeds channels 5 and 11

Input 2b feeds channels 2 and 8

Input 3 feeds channels 3, 6, 9, and 12

Breakers are UL 489 listed 10,000 AIC, 100% Switching Duty, Hydraulic-Magnetic

The following section cross references the UL ID module numbers and AMX Lighting module IDs.

The modules identified are the only ones that can be used in the RDA-ENC6B and RDA-ENC12B enclosures.