AMX specifications Specifications, RDM-3EM and RDM-6EM UL and C-Ul Ratings, Installation Sheet

Models: RDM-3EM RDM-6EM

1 2
Download 2 pages 16.56 Kb
Page 1
Image 1
Installation Sheet

Installation Sheet

RDM-3EM and RDM-6EMEnergy Management Modules

The RDM-3EM (FG606-81) and RDM-6EM (FG606-80) are 3 and 6 channel switching energy management modules. They are designed for use with the RDA series of enclosures in an AMX Lighting™ system.

For more detailed installation and operating instructions, refer to the Radia Lighting Control System Instruction Manual, available on-line at www.amx.com.

The RDM-3EM and RDM-6EM are designed with the most advanced latching energy management relays to support heavy duty commercial applications, building automation, and loadside management. Equipped with on-board module microprocessors, both support relay control and sequencing. Features include:

User selectable delays in sequencing mode to minimize inrush current and stress on the electrical distribution system.

Selectable strapping facilitates multiple relays on one Radia control channel for large area control.

Manual on/off override on each relay independent of control system.

Relays retain their state during power and control system outages.

Visual Status Indicators on each relay.

Latching relays do not consume any control current, except when they change state, eliminating the need for additional Radia power supplies.

 

 

 

 

Mounting

 

 

 

 

 

 

 

 

points

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

Relays

3

 

 

 

(1-6)

 

 

 

 

 

 

 

 

 

4

 

 

 

Control

Port

Strapping

Jumpers

(JP3 - JP4)

FIG. 2 RDM-3EM

 

 

 

Mounting

 

 

 

 

 

 

points

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

Relays

2

 

 

 

(1-3)

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

Sequencing

Delay Jumpers

(JP1 and JP2)

Mounting points

5

6

Control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Port

 

 

 

Sequencing

Strapping

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Delay Jumpers

Jumpers

 

 

 

 

 

 

(JP3 - JP7)

 

 

 

 

 

 

(JP1 and JP2)

 

 

 

 

 

 

 

Mounting points

FIG. 1 RDM-6EM

Specifications

Dimensions (HW): 10.00" x 2.75" (25.40 cm x 6.99 cm)

Non-phase dependant

Use wires rated at 75°C (167°F)

Torque terminals to 4.4 in lbs.

Wire size: 26 AWG to 10 AWG

Wire stripping length: 0.28" (7 mm)

Weight: 15 oz. (RDM-3EM) and 1.5 lbs. (RDM-6EM)

RDM-3EM and RDM-6EM UL and C-Ul Ratings

General purpose: 120, 240, 277, and 347* VAC, 20 A

UL/CUL916 Energy Management Systems.

UL/CUL508 Industrial Control Systems.

Suggested Switched Loads

Incandescent

Fluorescent

Transformer

Low voltage

General purpose

Caution: Pre-Installation Notes

All Class 1 wiring must be connected to proper terminals.

All control wiring must be connected to proper terminals.

Disconnect power while installing or connecting the unit.

Keep top and bottom air vents clear at all times.

Test loads for shorts before connecting.

Use low voltage wires with a 300 volt rating or greater.

Use field installed copper conductors.

All electrical ratings are for continuous duty.

For indoor use only.

Included Accessories

4 mounting screws

Control wiring harness

*Agency approval pending

Page 1
Image 1
AMX specifications Specifications, RDM-3EM and RDM-6EM UL and C-Ul Ratings, Suggested Switched Loads