Installation Sheet
RDM-HFDB Heavy Duty FDB Module 2400 W
The
•Use field installed copper conductors.
•All electrical ratings are for continuous duty.
•For indoor use only.
•This module may require extra power from the AXlink connection or an external power supply connected to the control card.
Connecting the RDM-HFDB to the AMX Lighting Master
Mounting points
High
Neutral connectionsvoltage Line in (hot)
Positive air gap relay
Switched out |
| High |
| voltage | |
Dimmed out |
| |
| connections | |
|
|
Solid state relay
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)
3
2(AC)
1 (+)
Note: The
FIG. 2 Connecting the
Lighting Application Drawings
|
|
| All neutrals are common |
|
|
| to the Neutral block in |
|
|
| the enclosure. Provide |
|
| Neutral | a separate neutral for each |
Line in (HOT) |
| load. | |
|
| ||
|
| Florescent Ballast | |
|
|
| |
Neutral |
| Ballast | |
|
| Switched | |
| NEUTRAL LINE | SWITCHED DIMMED |
|
|
| Dimmed |
FIG. 1
RDM-HFDB UL and C-UL Ratings
•120 VAC, 2400 W
•240/277 VAC, 2400 W
Circuit breaker panel
Suggested Dimmed Loads
FIG. 3
•Lutron© FDB Ballasts
•Lutron
Specifications:
•Dimensions (HW): 10.0" x 2.75" (25.4 cm x 6.99 cm)
•Phase dependant
•Use wires rated at 75°C (167°F)
•Torque terminals to 20
•Max. wire size: 10 AWG (4 mm²)
•Wire stripping length: 0.28" (7 mm)
•Weight: 1.50 lbs. (0.680 kg)
•BTU/hr: 150
•Control current: 135 mA @ 12 VDC
•Use Dimming Curve 6 (refer to the Programming AMX Lighting instruction manual for more information).
•For use with FDB ballasts.
Caution: Pre-Installation Notes
•All Class 1 wiring must be connected to proper terminals.
•All control wiring must be connected to proper terminals.
•Disconnect power while installing or connecting the unit.
•Keep top and bottom air vents clear at all times.
•Test loads for shorts before connecting. Use