Installation Sheet

RDM-INC50 Incandescent Dimmer Module 6000 W

The RDM-INC50 Incandescent Dimmer Module is a standard 6000 W incandescent dimmer. It can dim incandescent lights, cold-cathode, neon transformers and two-wire dimmable ballasts. It is designed for use with the RDA series of enclosures, in a AMX Lighting™ modular digital dimming system. The RDM-INC50 module's 120, 240, and 277 VAC ratings are CE, UL, and C-UL approved.

Mounting points

Line in (hot)

Load out

500µS choke

50 A Power

Device

Low-voltage control wiring: 4-pin connector to AMX Lighting master controller

All electrical ratings are for continuous duty.

AC lighting loads only.

For indoor use only.

This module may require extra power from the AXlink connection or an external power supply connected to the control card.

Connecting the RDM-INC50 to the AMX Lighting Master

Pin 4 (GND)

Pin 3 (RLY)

Pin 2 (DIM)

Pin 1 (+12 V)

RDM-INC50 4-pin module connector

2(-)

1(+)

4-pin plug from a RDM series module

Note: The 4-pin plugs from the module connector to the 4-pin connector on the master (black plug cover facing up).

FIG. 2 RDM-INC50 connections

Lighting Application Drawing

 

All neutrals are common to the

 

Neutral block in the enclosure.

 

Provide a separate neutral for

Neutral

each load.

 

Line in (HOT)

Load

 

FIG. 1 RDM-INC50

RDM-INC50 UL and C-UL Ratings

120 VAC, 6000 W

240/277 VAC, 6000 W

Suggested Dimmed Loads

Incandescent

Low-voltage

Neon, cold cathode

Two-wire, phase-controlled ballast

Specifications:

Dimensions (HW): 10.0" x 5.50" (25.4 cm x 13.97 cm)

Phase dependant

Use wires rated at 75°C (167°F)

Torque terminals to 16 in-lbs. (1.84 N/M)

Max. wire size: 8 AWG (10 mm²)

Wire stripping length: 0.28" (7 mm)

Weight: 7.0 lbs. (3.175 kg)

BTU/hr: 750

Control current: 45 mA @ 12 VDC

Occupies two enclosure spaces

Caution: Pre-Installation Notes

Neutral

Load

Two-wire dimmable ballast

FIG. 3 RDM-INC50 wiring application

Neutral

Load

Neon lights

(cold-cathode, on/off)

All Class 1 wiring must be connected to proper terminals.

All control wiring must be connected to proper terminals.

Disconnect power while installing or connecting the unit.

Keep top and bottom air vents clear at all times.

Test loads for shorts before connecting.

Run all control and low-voltage wires away from heat producing parts of the dimmer.

Each dimming circuit must have a separate neutral connection.

Use low-voltage wires with a 300 volt rating or greater.

Use field installed copper conductors.

Page 1
Image 1
AMX specifications Installation Sheet, RDM-INC50 Incandescent Dimmer Module 6000 W