CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM

1.The UPS, in conjunction with a network interface card, shall be capable of gracefully shutting down one or more operating systems during when the UPS is on reserve mode.

2.The UPS shall also be capable of using an RS232 port to communicate by means of serial communications to gracefully shut down one or more operating systems during an on battery situation.

3.5REMOTE UPS MONITORING

A. The following three methods of remote UPS monitoring shall be available:

1.Web Monitoring: Remote monitoring shall be available via a web browser such as Internet Explorer.

2.RS232 Monitoring: Remote UPS monitoring shall be possible via either RS232 or contact closure signals from the UPS.

3.Simple Network Management Protocol (SNMP): Remote UPS Monitoring shall be possible through a standard MIB II compliant platform.

3.6SOFTWARE COMPATIBILITY

A:The UPS manufacturer shall have available software to support graceful shutdown and remote monitoring for the following systems:

a.Microsoft Windows 95/98/XP

b.Microsoft Windows NT 4.0 SP6/2000

c.OS/2

d.Netware 3.2 – 5.1

e.MAC OS 9.04, 9.22, 10

g. Digital Unix/True 64 h. SGI 6.0-6.5

j. SCO UNIX

k. SVR4 2.3, 2.41

m. SCO Unix Ware 7.0 - 7.11 n. SUN Solaris 2.6-2.8

o. SUN OS 4.13, 4.14

p. IBM AIX 4.3x-4.33g, 5.1 q. HP-UX 9.x-11.i

Part 4 - EXECUTION

4.1FACTORY ASSISTED START-UP

If a factory assisted UPS start-up is requested, factory trained service personnel shall perform the following inspections, test procedures, and on-site training:

A.Visual Inspection:

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM

Page 12
Image 12
APC LX a. Microsoft Windows 95/98/XP b. Microsoft Windows NT 4.0 SP6/2000, c. OS/2 d. Netware 3.2 e. MAC OS 9.04, 9.22