TROUBLE SHOOTING GUIDE (CONTINUED)
Pleat
Spacer
Figure 12
End Panel
“PRESS
TO OPEN”
Conductive
Rubber Strip
6.Inspect components to ensure the following (continued):
c.The conductive rubber strip must be in contact with the
d.The nine ionizing wires must be clean, straight, and hooked onto the bus bar at one end and the ionizer frame at the other. See Figure 11.
e.The control electrode must be properly inserted in the ionizer frame.
f.There must be no debris bridging the gap between the ionizing wires and any other component.
7.If a Model 51 is used:
a.Measure the current for the wire under the bracket - this must be 4 amps or more.
b.Ensure the Model 51 is at least 4” away from any transformer.
8.
9.Plug in the unit and turn it on.
10.Turn on the furnace/air handler blower.
11.After the blower starts, check unit for proper operation.