MODEL 8028 DAMPER POWER DISTRIBUTION PANEL
INSTALLATION INSTRUCTIONS & APPLICATION SHEET
WARNING |
| CAUTION |
|
|
|
1.120 volts may cause serious injury from electrical shock. Leave power to all system components disconnected until installation is complete
1.Installation must be done in accordance with the NEC and all other applicable local codes.
2.To prevent excessive transformer heating, do not power more than the recommended number of dampers to a transformer.
SPECIFICATIONS
|
|
|
Voltage |
| 24 VAC ±20% |
| ||
Max. Damper Power Input per Zone |
| 100VA max @ 24 VAC |
Damper Fuse Size |
| 5A Fast Acting (spare supplied) |
Control Input Current Draw (Zone A and Zone B) |
| 50 mA @ 24 VAC |
Max. No. of Aprilaire Dampers per Zone |
| 10 (refer to Diagram 3 on the back if there are |
|
| more than 10 dampers in a zone) |
Max Wire Size |
| 18 AWG |
Application Temperature/RH |
| 158°F / 90% RH |
|
|
|
Damper Power Input(s) from Transformers
|
| 5 | 4 | 3 | 2 | 1 |
|
|
|
| ZONE A |
|
|
|
|
|
|
| DAMPERS |
|
|
|
|
|
| |
|
| SINGLE |
| ZONE A |
|
| ||
POWER A | SINGLE | SUPPLY |
| ZA | ZONE A | |||
|
|
|
|
|
| NO | ||
|
|
|
|
|
|
| ||
|
|
|
|
|
|
| C | |
POWER B |
|
|
| ZONE B |
| NO | ||
| SEPARATE |
|
|
|
| ZB | C | |
|
|
|
|
|
| |||
| SUPPLIES |
|
|
|
| ZONE B | ||
|
|
|
|
|
| |||
|
| ZONE B |
|
|
|
|
|
|
| DAMPERS |
|
|
|
|
|
|
SPARE FUSE
5 4 3 2 1
Control Input(s) from Zoned Comfort Control Panel
Dampers Wired to ZONE A and ZONE B Terminals
SWITCH SETTINGS AND LED’S
Set to SINGLE SUPPLY when used:
• in a two zone system when there are no more than 10 dampers in either ZONE A or ZONE B.Power Supply Switch Size the transformer for the zone with the most dampers.
•when there are no more than 10 total dampers wired to ZONE A plus ZONE B. Size the transformer
for the total number of dampers connected to both zones.
When set to SINGLE SUPPLY, wire transformer to “POWER A” terminals. Refer to Diagram 2 on the back for wiring.
Set to SEPARATE SUPPLIES for all other applications. Wire transformers to “POWER A” and “POWER B” terminals. Refer to Diagram 1 on the back.
Zone LED’s
ZA LED lights when
ZB LED lights when