On Power
True On Line Sinewave Double Conversion UPS
TECHNICAL FEATURES
MODEL |
| |
Power Rating |
| 6000 VA - 4200 W |
INPUT | Voltage (Vac) | |
| Frequency (Hz) | 50 ± 5% (Auto Sensing) |
| Phase | SingleLine+Neutral+Ground |
| Input Power Factor | > 0.99 (Full Load) |
OUTPUT | Voltage (Vac) | 220/230/240 |
| Voltage Regulation | ± 2% |
| Voltage Adjustement | ± 0%; ± 1%; ± 2%; ± 3% |
| Frequency Stability | ±0.2% (Free Running) |
| Frequency Regulation | ± 1%; ± 3% |
| Wave Form | Sine Wave, THD<4% |
|
| (no load to full load) |
| Rated Power Factor | 0.7 |
| Transfer Time | 0 ms |
| Crest Factor | 3:1 |
| Efficiency (AC to AC) | >90% (Normal) |
| Efficiency | >98% (ECO) |
| (AC to AC, ECO) |
|
| Run Time (Full Load) | > 8 min |
| DC Start | Yes |
BATTERY | Type | Maintenance Free Sealed |
|
| Lead Acid |
| Quantity (pcs) | 20 |
| Voltage (Vdc) | 240 |
| Recharge Time | 4 Hours to 90% |
| Supplem. Charger | Optional 1000W Isolated |
|
| chargers |
PROTECTION | Short Circuit | Hold Whole System |
| OverHeat | Switch to Bypass |
| High Voltage Trip | Switch to Backup Mode |
| Battery Low | Alarm and Switch Off |
| Noise Suppression | Complies with |
| Spike Suppression | Complies with |
| OverLoad | AC Mode: |
|
| 1) <105% continuously Alarm |
|
| 2) |
|
| seconds before switching to bypass |
|
| 4) >150% immediately |
|
| switching to bypass |
|
| Backup Mode: Same Delay |
|
| Time as AC Mode, then |
|
| completely shutdown |
MODEL |
| |
ALARMS | Audible and Visual | Line Failure, Battery Low, Tranfer to Bypass, |
|
| System Fault Conditions |
DISPLAY | Self Diagnostics | Push Button (On Demand) |
| LED+LCD | Utility, Battery, Inverter, Bypass, |
|
| OverLoad, Load/Battery Level and Fault |
PHYSICAL | Dim (WxDxH) | 290 x 645 x 748 mm |
| Outlets | Terminal Block |
| Net Weights (Kgs) | 80 |
ENVIRONMENTAL | Operating |
|
| Temperature |
|
| Temperature Warning | The battery design life is based on a |
|
| temperature of 25o°C. Ambient temperature |
|
| above this range will reduce battery life |
| Altitude / Humidity | |
|
| 90% RH Humidity max |
| Noise | < 45 dB (at 1 metere) |
COMPUTER | Interface Type | Standard RS232 Interface / SNMP |
INTERFACE |
|
|
| Protocol | MEGATEC Protocol |
| AS 400 Interface | Optional As400/ Basic Photo Contact |
|
| Interface Board provides Utility Failure, |
|
| Battery Low, Bypass Active, UPS |
|
| Shutdown functions |
| SNMP Adaptability | Slot for Standard SNMP Card |
| Compatibility of | UPSilon2000 for: Novell NetWare, |
| Bundled Software | Windows95/98, Windows NT, Windows ME, |
|
| |
|
| Windows 2000 and XP, Linux and FREE BSD |
| Optional Software | UPSilion for UNIX, SNMP Adapter, USBMate |
SAFETY | Quality Assurance | ISO9001 Certified Company |
CONFORMANCE |
|
|
| Marks | CE |
ATLANTIS LAND S.p.A. - Viale De Gasperi 122 - 20017 Mazzo di Rho - Milano - ITALY | Subject to change without notice |
Phone: +39 - (0)2 - 93.90.60.85 Fax: +39 - (0)2 - 93.90.61.61 - Web: |
|