THERMOSTAT INSTALLATION (MODEL 2H2C)
FURNACE - MODEL 2540 MUST USE THIS THERMOSTAT
The thermostat is very sensitive. HANDLE WITH CARE AT ALL TIMES.
Locate thermostat 48˝ to 54˝ above floor on an INTERIOR wall. Pick a dry area where air circulation is good. EXTERIOR wall location must have a 3/4˝ spacer between thermostat and exterior wall.
1.Be sure all electrical power has been disconnected from the air con- ditioner, furnace and the power supply.
2.Do not install the thermostat where there are unusual heating condi- tions: such as direct sunlight, heat producing appliances (television, radio, wall lamp, etc.) or a furnace or air conditioner supply register.
3.ATTACHING THE WALL THERMOSTAT. Separate the thermostat body from the
SYSTEM CHECKS
NOTE: A SOFT lockout is a condition that is timed and will make addition- al attempts to correct the problem. A HARD lockout requires reset of the thermostat or turning the power switch off then back on.
PROPANE GAS PRESSURE TEST
The furnace and any individual
Before furnace is connected piping systems must be tested to be leak free. The test must maintain air pressure of at least 6˝ of mercury or 3 PSI for at least 10 minutes.
The entire piping system must be maintained within a range of
STATIC PRESSURE TEST
CASING STATIC PRESSURE TABLE
If duct static pressure cannot be set, casing static pressure should not exceed the values listed below when taken cold.
WARNING
FIRE OR EXPLOSION
•Never check for leaks with an open flame.
DIAGNOSTIC CHART
A diagnostic LED is located inside the exterior access cover on the out- side edge of the horizontal (2) stage control board. The following graph defines the codes.
| NUMBER OF LED FLASHES | DIANOSTIC INFORMATION | LOCKOUT |
| 1 | Low Input voltage | SOFT |
| 2 | Ignition Failure | SOFT |
| 3 | Open High Limit | SOFT |
| 4 | Stuck Sail Switch | HARD |
| 5 | Module Fault | HARD |
|
|
|
|
DUCTING SYSTEM | OPERATING VOLTS | FLEXIBLE | HARD |
DC MODELS | 12 | 0.25˝ W.C. | 0.35˝ W.C. |
Voltage greater than indicated will cause higher static readings. Reducing the number of duct turns and stretching ducts will increase air flow and reduce static pressure. Adding ducts or increasing dis- charge system (hard ducting) will also reduce static pressure. NOTE: Special tool required to take casing static pressures.
Location for Static Pressure Tap for casing is on the back of casing (top left corner) (FIG 3).
2-STAGE - MODEL 2540
4 WIRING
ELECTRONIC
DIGITAL
THERMOSTAT
MOTOR
RED
BLACK
YELLOW
| +12 VDC |
|
|
|
| RED |
| +THERMO |
| 1 | 1 |
|
|
|
| 2 | 2 |
| BLUE | |
|
|
|
| |||
|
|
|
|
|
|
|
|
| 3 | 3 |
| YELLOW | |
|
| 4 | 4 |
| ||
|
|
| ||||
|
|
|
|
| GREEN | |
| 5 | 5 |
| |||
|
|
|
|
| ||
|
|
| 6 | 6 |
|
|
|
| BULK HEAD | ||||
|
| CONNECTOR |
CUSTOMER SUPPLIED WIRE
WHITE
LIMIT SWITCH
RED |
|
|
| IGNITION | ELECTRODE |
DUAL | CONTROL | CHASSIS |
| ||
CONTROL |
| |
| GROUND | |
6 5 4 3 21 |
| |
|
| |
WHITE |
| HIGH TENSION |
|
| |
BLACK | ORANGE | RED |
| BLUE | |
|
| |
| YELLOW |
|
BROWN
SAIL
SWITCH
CHASSIS
GROUND
IMPORTANT: If any original wire has to | VALVE |
be replaced, it must be replaced with | |
type 105˚C or it's equivalent. |
|
4