TH150 400-150-000-C 5/9/06 3/6
4. Configuration

4.1 Configuration Menus

1A model
Application
(section 4.2)
Default mode &
Output 1 type
(section 4.3.1)
NSB value
(section 5.6)
Output 1
min. opening
(section 4.3.2)
Maximum
setpoint
(section 4.6)
Minimum
setpoint
(section 4.6)
0
Internal sensor
0 Cool / 0-10V 1 1°C (2°F) 00%
Can be set
between 35°C
(95°F) and
’’minimum
setpoint + 1’’
Default value
is 35°C (95°F)
Can be set
between 10°C
(50°F) and
’’maximum
setpoint - 1’’
Default value
is 10°C (50°F)
1 Room 1 Heat / 0-10 V 2 2°C (4°F) 1 10%
2 Return 2Cool / 2-10 V 3 3°C (6°F) 2 20%
3 Supply 3 Heat / 2-10 V 4 4°C (8°F) 3 30%
4 Auto changeover 5 5°C (10°F) 4 40%
5 Limited cooling 6 6°C (12°F) 5 50%
7 7°C (14°F)
8 8°C (16°F)
9 9°C (18°F)
1F model
Application
(section 4.2)
Default mode
(section 4.3.1)
NSB value
(section 5.6)
Output 1
min. opening
(section 4.3.2)
Output 1
opening time
(section 4.3.3)
Maximum
setpoint
(section 4.6)
Minimum
setpoint
(section 4.6)
0
Internal sensor
0Cool 1 1°C (2°F) 00% 080
Can be set
between 35°C
(95°F) and
’’minimum
setpoint + 1’’
Default value
is 35°C (95°F)
Can be set
between 10°C
(50°F) and
’’maximum
setpoint - 1’’
Default value
is 10°C (50°F)
1 Room 1 Heat 2 2°C (4°F) 1 10% 1 90
2 Return 33°C (6°F) 2 20% 2 100
3 Supply 4 4°C (8°F) 3 30% 3 110
4 Auto changeover 5 5°C (10°F) 4 40% 4120
5 Limited cooling 6 6°C (12°F) 5 50% 5 130
7 7°C (14°F) 6 140
8 8°C (16°F) 7 150
9 9°C (18°F) 8 160
1A2T model
Application
(section 4.2)
Default mode &
Output 1 type
(section 4.3.1)
Output 2 typea
(section 4.4)
Output 3 type
(section 4.5)
Output 3
activation
(section 4.5)
NSB value
(section 5.6)
Output 1
min. opening
(section 4.3.2)
Maximum
setpoint
(section 4.6)
Minimum
setpoint
(section 4.6)
0
Internal sensor
0 Cool / 0-10V 0Not used 0 Not used 0 100% 11°C (2°F) 00%
Can be set
between 35°C
(95°F) and
’’minimum
setpoint + 1’’
Default value
is 35°C (95°F)
Can be set
between 10°C
(50°F) and
’’maximum
setpoint - 1’’
Default value
is 10°C (50°F)
1 Room 1 Heat / 0-10 V 1 SSR 24 VAC 1 SSR 24 VAC 1 10% 2 2°C (4°F) 1 10%
2 Return 2Cool / 2-10 V 2 N.C. Valve 2 N.C. Valve 2 20% 33°C (6°F) 2 20%
3 Supply 3 Heat / 2-10 V 3 N.O. Valve 3 N.O. Valve 3 30% 4 4°C (8°F) 3 30%
4 Auto changeover 4 Mech. relay 4 Mech. relay 4 40% 5 5°C (10°F) 4 40%
5 Limited cooling 5 SSR 3-32 V 5 Contact 5 50% 6 6°C (12°F) 5 50%
6 SCR 0-10 V 6 60% 7 7°C (14°F)
7 Act. 0-10 V 7 70% 8 8°C (16°F)
8 Act. / 2-10 V 8 80% 9 9°C (18°F)
9 90%
a. If Output 2 type is set to 0-4, set the SW6 switch to Triac. If the output type is set to 5-8, set the switch to Analog (see section 4.7).
1F2T model
Application
(section 4.2)
Default mode
(section 4.3.1) Output 2 typea
(section 4.4)
Output 3 type
(section 4.5)
Output 3
activation
(section 4.5)
NSB value
(section 5.6)
Output 1
min. opening
(section 4.3.2)
Output 1
opening time
(section 4.3.3)
Maximum
setpoint
(section 4.6)
Minimum
setpoint
(section 4.6)
0
Internal sensor
0Cool 0 Not used 0 Not used 0 100% 11°C (2°F) 00% 080
Can be set
between
35°C (95°F)
and ’’min
setpoint + 1’’
Default
value is
35°C (95°F)
Can be set
between
10°C (50°F)
and ’’max
setpoint - 1’’
Default
value is
10°C (50°F)
1 Room 1 Heat 1 SSR 24 VAC 1 SSR 24 VAC 1 10% 2 2°C (4°F) 1 10% 1 90
2 Return 2 N.C. Valve 2 N.C. Valve 2 20% 33°C (6°F) 2 20% 2 100
3 Supply 3 N.O. Valve 3 N.O. Valve 3 30% 4 4°C (8°F) 3 30% 3 110
4 Auto changeover 4 Mech. relay 4 Mech. relay 4 40% 5 5°C (10°F) 4 40% 4120
5 Limited cooling 5 SSR 3-32 V 5 Contact 5 50% 6 6°C (12°F) 5 50% 5 130
6 SCR 0-10 V 6 60% 7 7°C (14°F) 6 140
7 Act. 0-10 V 7 70% 8 8°C (16°F) 7 150
8 Act. / 2-10 V 8 80% 9 9°C (18°F) 8 160
9 90%
a. If Output 2 type is set to 0-4, set the SW6 switch to Triac. If the output type is set to 5-8, set the switch to Analog (see section 4.7).
nRemove the thermostat from its base and
set the SW2 switch to MENU.
oReinstall the thermostat. The thermostat is
now in configuration mode. The first digit
flashes to indicate that the first item of the
menu can now be modified.
pTo modify the setting, use the up/down
arrows. Refer to the adjacent tables.
qPress Override to save the new setting and
go to the next item.
rRepeat steps 3 and 4 for remaining items.
sWhen the configuration is done, set the
SW2 switch back to NORMAL.
NOTE: Factory settings are
inside the shaded cells.