5.OTHER INSTALLATIONS – Many other installations are possible with the packaged air conditioner. No matter what the installation, always consider the following facts:

A.Insure that the discharge air is not obstructed in any way so as to cause operation difficulties.

B.The indoor coil drain pan is equipped with a coupling that must be piped through a condensate drain trap to a suitable drain.

C.Always mount the unit is such a position that it may be easily reached for servicing and maintenance.

D.Insure that the unit is clear so that proper air flow over the outdoor coil will be maintained.

If this unit is operated in cooling below a 55° outdoor ambient temperature, the installation of low ambient controls (CMA-28) to unit is required.

CONDENSATE DRAIN TRAP

It is very important to provide a trap in the condensate drain line to allow a positive liquid seal in the line and assure correct drainage from the coil condensate pan.

Install condensate drain trap shown in Figure 8. Use drain connection size or larger. Do not operate unit without trap. Unit must be level or slightly inclined toward drain. With a trap installed on a unit located in an unconditioned area, water in the trap may freeze. It is recommended that the trap material be of a type that will allow for expansion of water when it freezes.

AIR FILTERS

Air filters for the return air side of the system are not provided as part of these models, and must be field supplied and installed as part of the final installation.

Prior thought should be given to return air location and placement of the air filter(s). The air filter(s) must be of adequate size and readily accessible to the operator of the equipment. Filters must be adequate in size and properly maintained for proper operation. If this is not done, excessive energy use, poor performance, and multiple service problems will result. It is impossible to oversize air filters. Generous sizing will result in cleaner air and coils as well as lower operating costs and extend the time between required changes. Table 5 shows minimum filter areas and recommended filter sizes. Actual filter sizes can vary with the installation due to single or multiple returns utilizing a filter/grille arrangement or being placed immediately ahead of the indoor coil face in the return air duct.

TABLE 5

FILTER REQUIREMENTS & SIZES

Model No.

Minimum Filter Area

Recommended

Size

 

 

 

 

 

PA1324

462 Square Inches

 

PA1330

15 x 30-5/8 x 1

(3.21 Square Feet)

PA1336

 

 

 

 

 

 

PA1342

608 Square Inches

 

PA1348

(2) 16 x 20 x 1

(4.62 Square Feet)

PA1360

 

 

 

 

 

 

NOTE: If roof hood accessory is to be used, information on air filters may be found under that heading in this manual. Air filters are supplied as part of that package.

FIGURE 5

CONDENSATE DRAIN TRAP

MIS-136

Manual

2100-467

Page

12 of 23

Page 12
Image 12
Bard PA13421-A, PA13481-B, PA13481-A, PA13601-A, PA13421-B Condensate Drain Trap, AIR Filters, Filter Requirements & Sizes

PA13601-B, PA13481-A, PA13601-A, PA13481-B, PA13421-A specifications

Bard is a renowned name in the HVAC (Heating, Ventilation, and Air Conditioning) industry, known for its innovative products that ensure comfort and efficiency in various settings. The models PA13421-B, PA13421-A, PA13481-B, PA13601-A, and PA13481-A are prime examples of Bard's commitment to quality and technology, providing reliable performance and advanced features suitable for both commercial and residential applications.

The PA13421-B and PA13421-A are designed for energy efficiency, boasting high SEER (Seasonal Energy Efficiency Ratio) ratings that significantly reduce energy consumption without sacrificing performance. These units utilize a scroll compressor, which is known for its quiet operation and superior reliability. Additionally, they feature advanced microprocessor control systems that allow for precise temperature regulation and can be easily integrated into building management systems.

The PA13481-B and PA13481-A models are equipped with durable, heavy-gauge cabinets that protect the internal components from environmental factors, ensuring longevity and minimal maintenance. These units also incorporate a high-capacity airflow design, which improves indoor air quality by effectively circulating air throughout the space. The implementation of variable-speed blowers further enhances comfort levels by adjusting airflow based on real-time demand.

The PA13601-A model stands out with its versatility, as it can operate effectively in a wide range of climates. Its design includes a robust refrigerant management system that ensures optimal performance even in extreme temperatures, making it a favorite for users in harsher environments. This model also features a comprehensive diagnostic system that alerts users to potential issues before they escalate, facilitating proactive maintenance.

All these models emphasize sustainability, incorporating environmentally friendly refrigerants that comply with international regulations. Bard's dedication to reducing carbon footprints is evident in these units, which not only perform admirably but also contribute to a greener planet.

In summary, the Bard PA13421-B, PA13421-A, PA13481-B, PA13601-A, and PA13481-A models exemplify cutting-edge technology and superior engineering in the HVAC sector. With their energy-efficient designs, robust construction, and advanced control systems, these HVAC solutions provide reliable comfort for users while being mindful of environmental impact.