High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor contactor will de-energize immediately. The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay on break time has expired. If the high pressure switch opens again in this same operating cycle the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.

Low Pressure Switch, Bypass, and Lockout Sequence

If the low pressure switch opens for more than 120 seconds, the compressor contactor will de-energize and go into a soft lockout. Regardless the state of the low pressure switch, the contactor will reenergize after the delay on make time delay has expired. If the low pressure switch remains open, or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm relay circuit will energize. Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications where alarm relay is employed. This terminal is powered whenever compressor is locked out due to HPC or LPC sequences as described.

NOTE: Both high and low pressure switch controls are inherently automatic reset devices. The high pressure switch and low pressure switch cut out and cut in settings are fixed by specific air conditioner or heat pump unit model. The lockout features, both soft and manual, are a function of the Compressor Control Module.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break Timer

The potentiometer is used to select Delay on Break time from 30 seconds to 5 minutes. Delay on Make (DOM) timing on power-up and after power interruptions is equal to 2 minutes plus 10% of Delay on Break (DOB) setting:

0.5 minute

(30 seconds)

DOB = 123 second DOM

1.0 minute

(60 seconds)

DOB = 126 second DOM

2.0minute (120 seconds) DOB = 132 second DOM

3.0minute (180 seconds) DOB = 138 second DOM

4.0minute (240 seconds) DOB = 144 second DOM

5.0minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay.

Typical Settings for Dual Unit Installation:

Unit 1: DOB set at 2 minutes, and DOM is 132 seconds.

Unit 2: DOB set at 4 minutes, and DOM is 144 seconds.

PHASE MONITOR

All units with three phase scroll compressors are equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two LEDs. If the Y signal is present at the phase monitor and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply leads to the unit. Do not reverse any of the unit factory wires as damage may occur.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all units so that the system operating pressures can be observed. A pressure table can be found later in the manual covering all models. It is imperative to match the correct pressure table to the unit by model number.

Manual 2100-351 Page 16

Page 18
Image 18
Bard WL6023, WL602N, WL4822, WL4823, WL6022 installation instructions Phase Monitor, Pressure Service Ports

WL6022, WL6023, WL4823, WL4822, WL602N specifications

Bard's WL6022, WL4822, WL4823, WL602N, and WL6023 represent a series of advanced heating and cooling units tailored for both residential and commercial applications. Each model embodies Bard's commitment to innovation, efficiency, and user-friendly operation, providing sustainable climate control solutions.

The WL6022 stands out with its powerful performance, designed for large spaces needing effective air distribution. With a robust heat capacity, this model can effectively maintain comfortable indoor temperatures even in extreme weather conditions. It incorporates advanced energy-saving technologies, such as a high-efficiency compressor, allowing users to keep operating costs low while ensuring reliable heating and cooling.

The WL4822 and WL4823 are more compact options, ideal for smaller residential or commercial areas. These models feature dual-speed fans, enhancing their efficiency while minimizing noise levels. The WL4823 comes equipped with additional smart control options, enabling users to customize their settings for optimized comfort. Both models benefit from innovative insulation techniques that reduce energy loss, making them environmentally friendly choices.

The WL602N model is a notable addition, designed with energy efficiency at its core. It utilizes a microprocessor-based control system that allows precise temperature management, further optimizing energy usage. Additionally, the WL602N supports advanced diagnostics, making maintenance easier and reducing downtime.

Finally, the WL6023 model is engineered for versatility, accommodating various installation demands. Its flexible design allows it to be used in diverse environments, ensuring it meets the cooling and heating needs of any space. The WL6023 is recognized for its airflow control features, which ensure even temperature distribution throughout the room.

In conclusion, Bard's WL6022, WL4822, WL4822, WL602N, and WL6023 models exemplify modern engineering in climate control technology. Their blend of efficiency, performance, and smart features positions them as reliable choices for effective heating and cooling. Whether used in homes or industrial settings, these models are designed to deliver superior comfort while minimizing energy consumption. Bard continues to lead the way in crafting innovative climate solutions, ensuring customer satisfaction and environmental responsibility.