Fire Alarm Systems D125B Dual Class B Initiating Module
D125B Dual Class B Initiating Module
www.boschsecurity.com
The D125B has two separate NFPA Class B (Style B) powered loops. The module supervises each of the loops for opens, shorts, or ground faults. Both loops can be powered with either 12 VDC or 24 VDC to connect compatible
The D125B is suitable for connecting fire or burglary devices in commercial, industrial, and institutional applications. Schools, offices, and health care facilities are typical commercial applications.
Functions
Loop Supervision
The D125B needs to be electrically connected to earth ground and to the control panel's common. The D125B has a supervisory output terminal for each of its loops. All terminal designations are clearly marked on the module circuit board.
To supervise the loops, install an
(P/N:
uTwo separate powered detector loops
uSuitable for 12 VDC or 24 VDC, two‑wire or four‑wire detectors
uUp to 50 two‑wire 12 VDC glass break detectors
uReports individual loop alarm, individual loop trouble, and ground fault
uManually resets latching devices from control panel or remote central station
adding additional devices to an existing system, use the 1.8 kΩ resistor (P/N: F01U009011) supplied with the module.
The D125B shorts the protective loop on the control panel when the high (+) and low
•Either of the module protective loops are opened.
•The D125B Interface module is unpowered.
•Either the high (+) side of the loop or the low
With the D9412GV3, D7412GV3, D7212GV3, D9412GV2, D7412GV2, D7212GV2, D9412G, D7412G, and D7212G Control Panels, a short to ground causes a ground fault condition when ground fault detect is enabled.
When programming for fire applications, refer to the appropriate control panel's operation and installation guide.
Notice
Do not mix 12 VDC and 24 VDC detectors on the same D125B Module.