Bosch Appliances F220B6RS Certifications and Approvals, Installation/Configuration Notes

Models: F220B6RS

1 4
Download 4 pages 36.31 Kb
Page 2
Image 2
Certifications and Approvals

2 F220B6RS 24 VDC Fourwire Detector Base with Sounder

the interconnected detector loop must not exceed 10 mA.

Certifications and Approvals

Region

Certification

 

USA

UL

ULSZ: Audible Signal Appliances (UL464),

 

 

UROX: Smoke - Automatic Fire Dectectors

 

 

(UL268), UROX7: Smoke - Automatic Fire

 

 

Dectectors Certified for Canada (ULC-

 

 

S529)

 

FM

 

 

CSFM

1700-1615: 105

 

NYC-MEA

(117-05-E)

Installation/Configuration Notes

Compatibility Information

Fourwire: Compatible with all UL Listed fourwire control panels. Refer to the control panel's Installation Instructions for proper endofline (EOL) resistor selection.

Detectors: Compatible with the following F220 Series Detector Heads:

F220P Photoelectric Smoke Detector

F220PTH Photoelectric Smoke Detector with +135°F (+57°C) Heat Sensor

F220PTHC1 Photoelectric Smoke Detector with +135°F (+57°C) Heat Sensor and Carbon Monoxide Sensor Enhancement1

F220135 Electronic RateofRise, Fixed Temperature +135°F (+57°C) Heat Detector

F220135F Electronic Fixed Temperature +135°F (+57°C) Heat Detector

F220190F Electronic Fixed Temperature +190°F (+88°C) Heat Detector

1The F220PTHC detects carbon monoxide (CO) as a component of a fire. It is not a CO detector and cannot activate an alarm in the presence of CO only.

Mounting Considerations

Depending on local regulations, surface mount the bases using anchors, mollies, or wing nuts, or mount directly on fourinch square or octagonal electrical boxes or singlegang switch boxes.

Note The electrical box must be large enough to accommodate the number and size of conductors specified by the National Electrical Code or any local authorities having jurisdiction (AHJ).

Wiring Considerations

In a four-wire system, the maximum loop length and number of bases that can be placed on a loop depend on the voltage drop on the power circuit. Use standard voltage drop calculations to ensure that the last detector on the loop has at least 16 V when all sounders and relays are powered.

Parts Included

Quant. Component

1Detector base

1Literature pack

Technical Specifications

Environmental Considerations

Relative Humidity:

0 to 95%, noncondensing; 15% to 95%,

 

noncondensing when used with CO sensor

 

model

Temperature (operating):

+32°F to +100°F (0°C to +38°C)

Mechanical Properties

Color:Off-white

Dimensions (diameter x thick- 6 in. x 0.9 in. (15.2 cm x 2.3 cm) ness)

Material:

Fireresistant plastic

Outputs

 

Relay Type:

Normallyopen (NO) Form A

Relay Rating:

0.5 A at 120 VDC or 120 VAC

Sounder Output:

>85 dB at 10 ft (3 m)

Power Requirements

 

Voltage Range:

16.0 VDC to 30 VDC

Alarm Current

 

6-wire mode (4-wire base + two sounder power wires)

Relay:

The relay draws 15 mA in alarm.

Steady Sounder:

24 VDC: 30 mA

 

30 VDC: 35 mA

4-wire mode

 

With Steady Sounder

24 VDC: 45 mA

and Relay:

30 VDC: 50 mA

Standby Current (base only):

30 VDC: 10 mA maximum

Page 2