2 F220‑B6RS 24 VDC Four‑wire Detector Base with Sounder
the interconnected detector loop must not exceed 10 mA.
Certifications and Approvals
Region | Certification |
|
USA | UL | ULSZ: Audible Signal Appliances (UL464), |
|
| UROX: Smoke - Automatic Fire Dectectors |
|
| (UL268), UROX7: Smoke - Automatic Fire |
|
| Dectectors Certified for Canada (ULC- |
|
| S529) |
| FM |
|
| CSFM | |
|
Installation/Configuration Notes
Compatibility Information
Four‑wire: Compatible with all UL Listed four‑wire control panels. Refer to the control panel's Installation Instructions for proper end‑of‑line (EOL) resistor selection.
Detectors: Compatible with the following F220 Series Detector Heads:
•F220‑P Photoelectric Smoke Detector
•F220‑PTH Photoelectric Smoke Detector with +135°F (+57°C) Heat Sensor
•F220‑PTHC1 Photoelectric Smoke Detector with +135°F (+57°C) Heat Sensor and Carbon Monoxide Sensor Enhancement1
•F220‑135 Electronic Rate‑of‑Rise, Fixed Temperature +135°F (+57°C) Heat Detector
•F220‑135F Electronic Fixed Temperature +135°F (+57°C) Heat Detector
•F220‑190F Electronic Fixed Temperature +190°F (+88°C) Heat Detector
1The F220‑PTHC detects carbon monoxide (CO) as a component of a fire. It is not a CO detector and cannot activate an alarm in the presence of CO only.
Mounting Considerations
Depending on local regulations, surface mount the bases using anchors, mollies, or wing nuts, or mount directly on four‑inch square or octagonal electrical boxes or single‑gang switch boxes.
Note The electrical box must be large enough to accommodate the number and size of conductors specified by the National Electrical Code or any local authorities having jurisdiction (AHJ).
Wiring Considerations
In a
Parts Included
Quant. Component
1Detector base
1Literature pack
Technical Specifications
Environmental Considerations
Relative Humidity: | 0 to 95%, non‑condensing; 15% to 95%, |
| non‑condensing when used with CO sensor |
| model |
Temperature (operating): | +32°F to +100°F (0°C to +38°C) |
Mechanical Properties
Color:Off-white
Dimensions (diameter x thick- 6 in. x 0.9 in. (15.2 cm x 2.3 cm) ness)
Material: | Fire‑resistant plastic |
Outputs |
|
Relay Type: | Normally‑open (NO) Form A |
Relay Rating: | 0.5 A at 120 VDC or 120 VAC |
Sounder Output: | >85 dB at 10 ft (3 m) |
Power Requirements |
|
Voltage Range: | 16.0 VDC to 30 VDC |
Alarm Current |
|
Relay: | The relay draws 15 mA in alarm. |
Steady Sounder: | 24 VDC: 30 mA |
| 30 VDC: 35 mA |
| |
With Steady Sounder | 24 VDC: 45 mA |
and Relay: | 30 VDC: 50 mA |
Standby Current (base only): | 30 VDC: 10 mA maximum |