Installation/Configuration Notes
•Manual call points have to be mounted visibly along escape and rescue routes (e.g. exits, passageways, stairwells) and be easily accessible.
•An installation height of 1400 mm ±200 mm, meas- ured from the middle of the manual call point to the floor, must be maintained.
•Manual call points must be illuminated sufficiently with daylight or another light source (including emer- gency lighting, if present).
•Max. one test detector may be used for primary lines together with automatic detectors. The test detector is connected at the end of the primary line.
•Further standards, guidelines and planning recom- mendations regarding the installation location etc., should also be taken into consideration (see Fire De- tection manual).
•Regulations of local fire departments must be ob- served.
Installation
•Cables can be inserted
Ø 3,4
•Installation in fire hose cabinets is possible in three ways:
1 |
|
| 135° |
| 2,5 |
2 |
|
| 140° |
2 | 10 |
3 |
|
| 147 |
139 |
|
Pos. | Description |
1 | Installation depth version 1: 36 mm |
2 | Installation depth version 2: 14 mm |
3 | Installation depth version 3: approx. 30 mm |
Technical Specifications
Electrical
Operating voltage | 24 V DC (16.2 V DC . . . 30 V DC) |
|
|
Current consumption | Specified by the respective se- |
| curity system |
Mechanics |
|
|
|
Dimensions (W x H x D) | 135 x 135 x 37 mm / |
| 5.31 x 5.31 x 1.4 in. |
Housing material | Plastic (ASA) |
|
|
Colors | Red, RAL 3001 |
| Blue, RAL 5005 |
| Yellow, RAL 1003 |
Weight | Approx. 224 g |
|
|