Option Bus Accessories
FMR-1000-RCMD Remote Command Center
Remote operational terminal of the FPA-1000-UL panel, providing buttons for silence, reset, acknowledge and drill. Features scrolling keys, key switch with 1358 key and built-in piezo sounder.
FMR-1000-RA Remote Annunciator
Remote LCD annunciator featuring acknowledge key. Includes scrolling keys and built-in piezo sounder.
D7032 Eight-Zone LED Annunciator Expander Attaches to a D7030X, D7030X-S2 or D7030X-S8.
Identifies the location of a fire alarm for eight additional zones, showing 16 LED zones in the D7030X/D7032 combination.
D7048/B Octal Driver Modules
The outputs are fully programmable and can be activated by system events. These outputs have the same programming options as the local relays. Each output operates independently of the other seven to provide complete flexibility.
D7035/B Octal Relay Module
The FPA-1000-UL supports up to two Octal Relay Modules. The outputs are fully programmable and can be activated by system events. These outputs have the same programming options as the local relays. Each output operates independently of the other seven to provide complete flexibility.
D7030X LED Annunciator
Identifies the location of a fire alarm for up to eight zones allowed per system.
D7030X -S2 LED Annunciator
Features two zones reserved for supervisory functions. Incorpo- rates power and trouble LEDs plus eight-zone LEDs that can be individually labeled.
D7030X-S8 LED Annunciator
Features eight zones reserved for supervisory functions. Incorpo- rates power and trouble LEDs plus eight-zone LEDs that can be individually labeled.
Control Panel Accessories
FPP-RNAC-8A-4C Remote Notification Appliance Circuit Power Supply
The FPP-RNAC-8A-4C Remote NAC Booster adds four additional Notification Appliance Circuits: NFPA 72, Class B (Style Y) or Class A (Style Z) to the fire panel or serves as a power supply for fire protective signaling systems.
D126 (12v 7ah), D1218 (12v 18ah), D1224 (12v 24ah), D1238 (12 38ah) Secondary Battery
2 x 12 V, 18 Ah maximum within enclosure or 40 Ah maximum external.
BATB-40 / BATB-80 Battery Box
Provides a single level (two-battery capacity) of battery storage with an optional shelf that increases the battery capacity to four batter- ies. BATB-80 includes a mounted shelf that holds up to
four batteries.
FPM-1000-SFMK Semi-flush Mounting Kit
Includes trim ring and mounting accessories.
FPE-1000-SLC Signaling Line Circuit Module
Provides a Signaling Line Circuit for connection of analog DCP de- vices to the FPA_1000_UL Compact Fire Panel. A second Signaling Line Circuit can easily be added by plugging in the FPE-1000-SLC to the mainboard. Nominal 39 V DC (30 to 40 V DC), 200 mA maximum (per SLC), power-limited, supervised.
FPE-1000-CITY City Tie Plug-in Module
Provides two circuits that can be programmed as Local Energy or Reverse Polarity module.
Programming Tool
D7050: Analog Device Programmer
Handheld device that programs address settings on EEPROM programmable analog devices. Includes base for detector head programming and two-module program adapter for module programming (for 4-in or single-gang back box). Shows the current analog value of a connected detector.
Initiating Devices
FAA-325-B6 Analog Detector Base
Compatible with all analog addressable detectors that use the advanced analog communication protocol, except the ALG-DH. 6 in (15 cm) diameter.
FAA-325-B4 Analog Detector Base
Compatible with all analog addressable detectors that use the advanced analog communication protocol, except the ALG-DH. 4 in (10cm) diameter.
FAP-325 Analog Photoelectric Smoke Detector
Detects optically dense smoke typical of fires involving materials such as soft furnishings, plastic and foam, which tend to smolder and produce large, visible smoke particles.
FAH-325 Analog Heat Detector
Detects heat in environments where smoke detectors are unsuitable because of the presence of system or cooking fumes, such as
a kitchen.
FAI-325 Analog Ionization Smoke Detector
For use in areas where early warning of superheated or flaming combustibles is expected. Also designed for use where outside Radio Frequency Interference (RFI) and other electrical interference are expected.
FAA-325-B6S Analog Sounder Base
Contains an addressable sounder that provides an audible alarm in the immediate vicinity. Compatible with all analog addressable detectors that use the advanced analog communication protocol, except the ALG-DH. Auxiliary powered. The Analog Sounder base’s address is programmed automatically. (For this device, the address of the mounted detector plus 127 come up to the sounder
base address.)
FFAD-325 Series Analog Duct Smoke Detector
Provides early detection of smoke and products of combustion present in air moving through HVAC ducts in commercial, industrial and residential applications.
Three types available:
e FAD-325-DH Analog Duct Smoke Detector Replacement Head
e FAD-325 Analog Duct Smoke Detector (with Housing) e FAD-325-R Analog Duct Smoke Detector with two Relays
(with Housing)
Accessories
e FAA-325-2.5 Testing Tube, 2.5 ft length e FAA-325-5 Testing Tube, 5 ft length
e FAA-325-10 Testing Tube, 10 ft length
FMM-325A/FMM-325A-D Analog Manual Pull Station
Fast response contact monitor module mounted in a corrosion- resistant, rugged, die-cast housing for single-gang mounting. Loop powered.
Input/Output Modules
FLM-325-CZM4 Conventional Zone Module
Monitors dry contacts (NO) devices such as two-wire conventional detectors and pull stations. Transmits the status of one zone
of devices back to the panel (25 maximum per zone; number depends on type of connected devices). Class A or Class B wiring is configured with a jumper on the module. Auxiliary powered. The number of Conventional Zone Modules (CZM) per SLC module is limited to 64.
FLM-325-2I4 Dual Input Monitor Module
Provides two independent contact monitoring circuits while utilizing only one address on the SLC. Can be programmed to monitor normally open or normally closed contact fire alarm and supervisory devices (NO EOL, NC EOL, NC no EOL). Supervises with Style B (Class B). Loop powered.
FLM-325-2R4 Dual Relay Module
Allows independent control of two Form C contacts (rated for 1.0 A at 30 VDC or 0.5 A at 125 VDC) for a variety of normally open (NO) and normally closed (NC) contact applications such as fan operation, elevator recall, door closure and auxiliary notification. Loop powered.
FLM-325-ISO Short Circuit Isolator
Isolates a shorted section on a specific polling circuit from the rest of the system to minimize the loss of devices.
FLM-325-N4 Supervised Output Modules
Provide a supervised pole reversal output used for acoustic and optical signaling devices or to trigger a Remote NAC Booster. Require a 24 VDC auxiliary input voltage. The output relay is rated to supply 2 A at 30 VDC. Provide Steady, Pulsing and Temporal Code 3 output pattern.
FLM-325-I Series Fast Response Contact
Monitor Modules
Designed for use with pull stations, water flow switches and other applications requiring the monitoring of dry contact alarm initiating devices. Can be programmed in NO EOL, NC EOL, NC no EOL.
Three types available:
e FLM-325-I4 with 4-in Back Box
e FLM-325-IS with Terminal Screws (future release) e FLM-325-IW with Pigtail (future release)