10 en Preparation | Fire Monitoring System |
|
|
1Preparation
Parts Included
Amount Components
1Installation CD for
1USB dongle
1Disk containing the dongle.crp file
Requirement
FMS can be used with the following panels
und BZ 500. Your PC must fulfill the following requirements:
Hardware | Description |
COM port | Max. 4 (one COM port per panel) |
Interfaces | USB/LPT |
Drives | |
CPU | min. 2 GHz |
RAM | 1024 MB (server), 512 MB (client) |
Hard drive memory | 10 GB |
Network card | 100 Mbit |
Software | Description |
Operating system | Windows 2000 SP4, Windows 2003 server, |
| Windows XP SP2 (not with Windows XP Home) |
|
|
Internet Explorer | Version 5.5 SP1 or 6.0 |
MSDE | Version MSDE 2000 SP3a |
Microsoft IIS | Version 5.0 (Windows 2000, Windows XP) |
| Version 6.0 (Windows 2003 server) |
|
|
Prepare detector check plan and floor plan
Perform the following steps before installation:
–Store the detector check plan for each panel on the computer. Detector check plans created with WinPara do not include system addresses. Those you have to add manually in the detector check plan.
–Store all floor plans in .dwf format in one folder. FMS automatically sorts the floor plans alphabetically according to file names. Determine the sequence of the floor plans using letters.
–a_reception.dwf = 1st element in FMS
–b_office.dwf = 2nd element in FMS
F.01U.032.785 A3 2007.05 | Installation Guide | Bosch Security Systems |