Bradford-White Corp DS140S, DS150S Installation Vent-Air Intake System Installation

Models: DS150S DS140S

1 40
Download 40 pages 58.71 Kb
Page 20
Image 20

Installation (Vent-Air Intake System Installation) continued-

Figure 9

7.Extend the three (3) inch (7.6 cm) diameter telescopic tube to its maximum length and slide the backing plate over it. Place the large end of the three (3) inch (7.6 cm) diameter telescopic tube through the hole in the outside wall. Insert the smaller end of the three (3) inch diameter (7.6 cm) telescopic tube into the flared end of the three (3) inch (7.6 cm) diameter

elbow, one (1) inch (2.5 cm) (or until seated). Drill three (3) 1/8 inch diameter holes, 120o apart, through the three (3) inch (7.6 cm) diameter elbow into the three (3) inch (7.6 cm) diameter telescopic tube. Fasten with three (3) #8 sheet metal screws (supplied). Adjust the overall length of the three (3) inch (7.6 cm) diameter telescopic tube so that 2-1/2 inches

(6.4 cm) extends beyond the outside wall. Drill three (3) 1/8 inch diameter holes, 120o apart, through the three (3) inch (7.6 cm) diameter telescopic tubes where the small and large sections overlap. Fasten with three (3) #8 sheet metal screws (supplied). Using the supplied special RTV silicone sealant, apply a sufficient amount to seal the joints (See Figure 10).

20

Page 20
Image 20
Bradford-White Corp DS140S, DS150S instruction manual Installation Vent-Air Intake System Installation