Installation

S19-220

Installation

Supplies Required:

(3) 3/8” wall fasteners and bolts

Pipe sealant

Piping to 1/2” NPT water supply inlet on unit

Piping to 1-1/4” NPT drain outlet for eyewash

Sign-mounting hardware

NOTE: Local codes may require the installation of a backflow prevention valve to complete proper installation. Compliance with local codes is the responsibility of the installer. Valve must be tested annually to verify that it is functioning properly. Backflow prevention valves are not included with the fixture and may be supplied by the contractor or purchased from Bradley Corporation.

Step 1: Install inlet drain fitting

NOTE: The top of the eyewash heads should be 33”–45” (838mm–1143mm) from the floor.

1.Position the inlet drain fitting over the 1-1/4” drain outlet pipe from wall.

2.Using the inlet drain fitting as a template, mark the bolt hole locations on wall OR install three suitable fasteners (supplied by installer) for 3/8” bolts in the wall at the marked hole locations.

3.Bolt the inlet drain fitting to the wall or wall fasteners using 3/8” bolts (supplied by installer).

Step 2: Assemble components

1.Assemble the remaining eyewash components as shown on page 4.

Apply pipe sealant (supplied by installer) to all male-threaded pipe joints.

Use a strap wrench around pipes when tightening to prevent pipe marring.

Step 3: Connect water supply

1.Connect the water supply piping to the 1/2” NPT inlet on the eyewash (piping supplied by installer).

2.Connect the tailpiece to the 1-1/4” NPT drain outlet on the eyewash.

3.Mount the safety sign to the wall using sign- mounting hardware (supplied by installer).

4.Open the water supply lines. Test for leaks and adequate water flow.

13-1/4"

(337mm)

Ø 10" (254mm)

15-1/2" (394mm) 4"

(102mm)

7-3/8"

 

(187mm)

 

2-1/4"

 

(57mm)

 

Ø 5/16"

 

7-1/4" (8mm)

5-1/4"

(184mm)

(133mm)

36" (914mm) Suggested Height

To Floor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30-1/2"

 

 

 

 

 

 

 

 

(775mm)

 

 

4-1/2"

 

Suggested

 

 

 

 

(114mm)

Height

 

 

 

 

 

 

To Floor

 

8-1/4"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(210mm)

Wall

NOTE: All dimensions assume standard thread engagement. Variations in manufacturing allow for +/- 1/8 (3mm) per threaded joint. To find the tolerance of a dimension, add the number of thread joints in between a dimension and multiply it by 1/8 (3mm).

Bradley Corporation • 215-158 Rev. W; ECN 08-503

2/4/08

3

Page 3
Image 3