Briggs & Stratton 30208 owner manual Receptacles, Cold Weather Operation, Stopping the Engine

Models: 30208

1 32
Download 32 pages 43.68 Kb
Page 10
Image 10
Stopping the Engine

3500W Portable Generator

Stopping the Engine

1.Turn OFF and unplug all electrical loads from generator panel receptacles. NEVER start or stop engine with electrical devices plugged in and turned ON.

2.Let engine run at no-load for several minutes to stabilize internal temperatures of engine and generator.

3.Turn engine off according to instructions given in the engine owner’s manual.

4.Move fuel valve to “Off” position.

RECEPTACLES

RECEPTACLES CAUTION

Receptacles may be marked with rating value greater than generator output capacity.

NEVER attempt to power a device requiring more amperage than generator or receptacle can supply.

DO NOT overload the generator. See “Don’t Overload Generator”.

120/240 Volt AC, 20 Amp, Locking Receptacle

Use a NEMA L14–20 plug with this receptacle. Connect a 4–wire cord set rated for 250 Volt AC loads at 20 Amps (or greater) (Figure 5).You can use the same 4–wire cord if you plan to run a 120 Volt load.

This receptacle powers 120/240 Volt AC, 60 Hz, single phase loads requiring up to 3,500 watts of power (3.5 kW) at 14.6 Amps for 240 Volts or two independent 120 Volt loads at 14.6 Amps each.The outlet is protected by push–to–reset circuit breakers.

120 Volt AC, 20 Amp, Duplex Receptacles

Each duplex receptacle (Figure 6) is protected against overload by a push–to–reset circuit breaker.

Figure 6 — 120 Volt, 20 Amp Duplex Receptacle

Use each receptacle to operate 120 Volt AC, single–phase, 60 Hz electrical loads requiring up to 1,750 watts

(1.75 kW) at 14.6 Amps of current. Use cord sets that are rated for 125 Volt AC loads at 15 Amps (or greater).

Figure 5 — 120/240 Volt AC, 20 Amp Receptacle

4-Wire Cord Set

240V

120V 120/240 Volt AC, 20 Amp, Locking Receptacle 120V

W (Neutral)

Y (Hot)

X (Hot)

NEMA L14-20

Ground (Green)

COLD WEATHER

OPERATION

Under certain weather conditions (temperatures below 40°F [4°C] combined with high humidity), your generator may experience icing of the carburetor and/or the crankcase breather system.To reduce this problem, you need to perform the following:

1.Make sure generator has clean, fresh fuel.

2.Open fuel valve (turn valve to open position).

3.Use SAE 5W-30 oil (synthetic preferred, see engine manual).

4.Check oil level daily or after every eight (8) hours of operation.

5.Maintain generator following “Maintenance Schedule” in engine manual.

6.Shelter unit from elements.

10

Page 10
Image 10
Briggs & Stratton 30208 owner manual Cold Weather Operation, Stopping the Engine, Volt AC, 20 Amp, Duplex Receptacles