Instruction Sheet

Kit # 313574
NG/LPG Fuel Conversion Kit
NG to LPG Conversion

Each generator system is delivered with a kit that includes the plug and jet required to convert the engine to use LPG fuel. The special insertion tool (#19618) is available through Briggs & Stratton.

NOTICE Only qualified personnel as specified in the product installation manual should attempt Natural Gas (NG) to Liquid Petroleum Gas (LPG) conversions. Installations

and conversions must strictly comply with all applicable codes, industrial standards and regulations. Proper tools and workmanship are required. Damage resulting from unauthorized personel will void manuafacturer’s warranty.

NOTICE Ensure that the fuel supply can deliver an engine inlet pressure of 11 to 14 inches water column.

8. Lift latches up on both sides of panel to release.

To Reconfigure for LP:

 

9.

Pull panel upward and out of grooves.

The generator is equipped with a removable roof and removable

10.

Repeat steps 8 & 9 to remove other side panel.

11.

Remove 6 screws from exhaust panel.

side panels to permit simple servicing.

 

1.

Open control panel door by inserting key into lock and turn

 

 

 

one quarter turn counterclockwise.

 

 

 

2.

Set generator’s circuit breaker to OFF position.

 

 

3.

Set control panel system switch to OFF.

 

 

 

4.

Remove 15 Amp fuse from control panel.

 

 

 

5.

Press roof latch down until roof pops up slightly.

 

 

 

NOT

 

 

 

FOR

 

 

 

 

REPRODUCTION

6.Lift roof up a little ways and slide back. Lift roof off of generator.

7.Rotate 4 knobs 1/4 turn and lift divider off.

12.Pull exhaust panel up and out of base.

13.Remove two screws and pull muffler cover off.