CAT.SCO2B/SCO2LB
TOP VIEW |
|
| SIDE VIEW | MOUNTING | ||
|
| BRACKET | ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
5.6"
2.0"
ARCHITECTURAL AND ENGINEERING SPEC
The combination smoke and carbon monoxide alarm shall be a BRK Model SCO2B and shall provide at a minimum the following features and functions:
1.An ionization smoke sensing chamber and an electrochemical CO sensor.
2.Powered by a supervised 9V alkaline battery and features a solid state piezo horn rated at 85dB at 10 ft. and the unit shall be capable of self restoring.
3.The unit shall perform self diagnostic tests and issue a malfunction warning (three chirps) if the unit malfunctions.
4.The unit shall have an "End of Life" signal. This signal should be capable of temporarily being silenced for up to 2 days. After about 2 days, the signal will resume. After about
5.A visual
6.The CO sensor is adjusted not to detect CO levels below 30 PPM and will not alarm when exposed to constant levels of 30 PPM for 30 days. It will alarm at the following levels: 400 PPM CO between 4 and 15 minutes, 150 PPM CO between 10 and 50 minutes and 70 PPM CO between 60 and 240 minutes.
7.Two Latching features: Alarm Latch to easily identify initiating alarm after alarm
condition has subsided. Low battery latch: to visually identify which unit is in low
battery condition. Two Silence Features: Alarm Silence to temporarily silence nuisance alarms. Low Battery Silence to silence low battery chirp for up to 8 hours.
8.Two Locking features - tamper resistant locking pins that lock battery drawer and/or alarm to mounting bracket.
9.The unit shall be capable of operating between 40°F (4°C) and 100°F (38°C) and relative humidity between 10% and 95%.
10.The unit shall contain mounting hardware and shall be listed for wall or ceiling mounting.
11.The unit shall at a minimum meet the requirements of UL217 and UL2034, CSFM, NFPA 72 and 720 and the ICC.
INSTALLATION OF ALARM
Installation of this smoke alarm must conform to NFPA 72. Always check your local building codes. Follow all instructions for placement as outlined in the user’s manual.
THE PARTS OF THIS SMOKE ALARM
TOP OF ALARM
1. Test/Silence Button
2. Power Light (Green)/ Smoke Alarm light (Red)
3. CO Alarm Light (Red)
4. Battery Drawer
5.Behind Cover: Alarm 85 dB horn
1 | 3 |
| BOTTOM OF ALARM |
|
|
| |
|
| 1. | Mounting bracket |
| 2 | 2. | Mounting slots (1 of 2) |
2 |
| 3. | Locking Pins |
3 |
| 4. | Battery Drawer Latch |
4 |
| 5. | Battery Drawer - Install |
5 |
|
| 9V battery here |
|
|
|
TECHNICAL SPECS
Alarm Dimensions: | 5.6” dia x 2.0”H |
Weight: | 7.6 oz |
Operating Voltage: | 9V battery powered |
|
|
Temperature Range: | 40°F (4°C) to 100°F (38°C) |
|
|
Humidity Range: | 10% to 95% relative humidity (RH) |
|
|
Audio Alarm: | 85dB at 10 feet |
|
|
Test/Silence: | Electronically simulates smoke condition or carbon |
| monoxide condition, causing the unit to alarm |
| Press and hold test/silence button |
|
|
Alarm Reset: | Automatic when smoke and/or CO clears |
Smoke Sensor: | Dual chamber ionization |
CO Sensor: | Electrochemical |
|
|
Indicator Lights/Sounds: |
|
DC Power: | Intermittent Green LED |
Local Alarm: | Red LED flashes rapidly |
Alarm Latch: | Red LED flashes 2 sec on/2 sec off after local alarm stops |
Low Battery Latch: | Green LED flashes on for 2 seconds, off for 2 seconds. |
| Note: Latching features are active for 15 minutes only. |
|
|
Listing: | Listed to UL217 and UL2034 Standards |
SHIPPING SPECS:
Individual Carton Dimensions | 5.69"L x 2.25"W x 5.59"H |
Weight | 0.59 lbs. |
Cube | 0.041 ft3 |
UPC | 0 29054 00089 7: SCO2B |
| 0 29054 00736 0: SCO2LB |
|
|
Master Carton Dimensions | 14.43"L x 6.19"W x 12.63"H |
Master Pack | 12 |
Weight | 7.6 lbs. |
Cube: | 0.65 ft3 |
I2of5: | 200 29054 00089 1: SCO2B |
| 800 29054 00736 6: SCO2LB |
|
|
Pallet Information |
|
Cases per Layer | 19 |
Number of Layers: | 3 |
Cases per Pallet: | 57 |
Units per pallet: | 684 |
Cube: | 42.2 ft3 |
Weight: | 498 lbs. |
BATTERY DRAWER LOCK
| Push locking pin through |
| |
Remove Pin | hole near battery drawer |
| |
on the back of the alarm. |
| ||
|
|
|
|
|
|
|
|
©2010 BRK Brands, Inc. a Jarden Corporation
Company (NYSE: JAH)
3901 Liberty Street Road Aurora, IL
| First Alert is a registered trademark of the First Alert Trust |
brkelectronics.com | BRK is a registered trademark of BRK Brands, Inc. |
| CM3080 |