→TABLE
UNIT SIZE | LIQUID |
| VAPOR |
| VAPOR (LONG LINE) | |||
Connection Diameter |
| Tube Diameter | Connection Diameter |
| Tube Diameter | Connection Diameter | Tube Diameter | |
|
|
| ||||||
018, 024 | 3/8 |
| 3/8 | 5/8 |
| 5/8 | 5/8 | 3/4 |
030, 036 | 3/8 |
| 3/8 | 3/4 |
| 3/4 | 3/4 | 7/8 |
042, 048 | 3/8 |
| 3/8 | 7/8 |
| 7/8 | 7/8 | |
060 | 3/8 |
| 3/8 | 7/8 |
| 7/8 | ||
|
|
|
|
|
|
|
|
|
NOTES:
1.Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult the Application Guideline and Service Manual— Air Conditioners and Heat Pumps Using Puron® .
2.Do not apply capillary tube indoor coils to these units.
→ | TABLE |
| ||
|
|
|
|
|
|
| REQUIRED FOR | REQUIRED FOR | REQUIRED FOR |
| ACCESSORY | SEA COAST | ||
| APPLICATIONS | APPLICATIONS* | APPLICATIONS | |
|
| |||
|
| (BELOW 55°F) | (OVER 50 FT) | (WITHIN 2 MILES) |
| Crankcase Heater | Yes | Yes | No |
| Evaporator Freeze Thermostat | Yes | No | No |
| Winter Start Control | Yes† | No | No |
| Accumulator | No | No | No |
| Compressor Start Assist | Yes | Yes | No |
| Capacitor and Relay | |||
|
|
|
| |
| MotorMaster® Control, |
|
|
|
| or | Yes | No | No |
|
|
|
| |
| Wind Baffle | See | No | No |
| Coastal Filter | No | No | Yes |
| Support Feet | Recommended | No | Recommended |
|
|
|
| |
| or | No | See | No |
| Hard Shutoff TXV |
|
|
|
| Ball Bearing Fan Motor | Yes‡ | No | No |
*For Tubing Sets between 50 and 175 ft, refer to the Application Guideline and Service Manual— Air Conditioners and Heat Pumps Using Puron® .
† Only when
‡ Required for
VII. MAKE PIPING CONNECTIONS
WARNING: Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death. Use all service ports and open all
CAUTION: Do not leave system open to atmosphere any longer than minimum required for installation. POE oil in compressor is extremely susceptible to moisture absorption. Always keep ends of tubing sealed during installation.
CAUTION: If ANY refrigerant tubing is buried, provide a 6 in. vertical rise at service valve. Refrigerant tubing lengths up to 36 in. may be buried without further special consideration. Do not bury lines over 36 in. in length.
CAUTION: To prevent damage to unit or service valves observe the following:
• Use a brazing shield.
•Wrap service valves with wet cloth or use a heat sink material.
Outdoor units may be connected to indoor section using accessory tubing package or
→ There are no
If refrigerant tubes or indoor coil are exposed to atmosphere, they must be evacuated to 500 microns to eliminate contamination and moisture in the system.
A. OUTDOOR UNIT CONNECTED TO FACTORY- APPROVED INDOOR UNIT
Factory refrigerant charge is for a 15 ft line set. Outdoor unit contains correct system refrigerant charge for operation with ARI rated indoor unit. Check refrigerant charge for maximum effi- ciency. The charge must be adjusted based on the actual line set length. Add or subtract 0.6 oz/ft for line sets longer or shorter than 15 ft.
B. INSTALL LIQUID-LINE FILTER DRIER
CAUTION: Installation of filter drier in liquid line is required.
Refer to Fig. 6 and install filter drier as follows:
1.Braze