Bryant 580J*16D instruction manual Unit Wire/Fuse or Hacr Breaker Sizing Data

Models: 580J*16D

1 4
Download 4 pages 40.38 Kb
Page 4
Image 4

580J*16D

Table 1 – Unit Wire/Fuse or HACR Breaker Sizing Data

 

 

 

COMBUSTION

POWER

 

 

NO C.O. or UNPWR C.O.

 

 

 

 

 

FAN MOTOR

EXHAUST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

NOM.

IFM

 

 

 

NO P.E.

 

w/ P.E. (pwrd fr/ unit)

 

 

 

 

 

 

 

 

 

 

 

V---Ph---Hz

TYPE

FLA

FLA

 

FUSE

DISC. SIZE

 

FUSE

DISC. SIZE

 

 

 

 

or

 

or

 

 

 

MCA

 

 

MCA

 

 

 

 

 

 

 

HACR

FLA

LRA

HACR

FLA

LRA

 

 

 

 

 

 

 

 

 

 

 

 

 

BRKR

 

BRKR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

 

68.3

80

71

396

72.1

80

76

400

 

208/230---3---60

MED

0.48

3.8

70.8

80

74

413

74.6

90

79

417

 

 

HIGH

 

 

77.8/75.8

100/100

82/80

424

81.6/79.6

100/100

87/84

428

580J*16D

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

 

34.0

45

35

234

35.8

45

37

236

 

 

 

 

 

460--- 3--- 60

MED

0.25

1.8

35.0

45

37

243

36.8

45

39

245

 

 

HIGH

 

 

38.2

50

40

248

40.0

50

42

250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

 

26.5

30

28

184

30.3

40

32

188

 

575--- 3--- 60

MED

0.24

3.8

26.5

30

28

184

30.3

40

32

188

 

 

HIGH

 

 

29.8

35

31

187

33.6

40

36

191

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 1 — Unit Wire/Fuse or HACR Breaker Sizing Data (cont)

 

 

 

COMBUSTION

POWER

 

 

 

w/ PWRD C.O.

 

 

 

 

 

 

FAN MOTOR

EXHAUST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

NOM.

IFM

 

 

 

NO P.E.

 

w/ P.E. (pwrd fr/ unit)

 

 

 

 

 

 

 

 

 

 

 

V---Ph---Hz

TYPE

FLA

FLA

 

FUSE

DISC. SIZE

 

FUSE

DISC. SIZE

 

 

 

 

or

 

or

 

 

 

MCA

 

 

MCA

 

 

 

 

 

 

 

HACR

FLA

LRA

HACR

FLA

LRA

 

 

 

 

 

 

 

 

 

 

 

 

 

BRKR

 

BRKR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

 

73.1

80

77

401

76.9

100

81

405

 

208/230---3---60

MED

0.48

3.8

75.6

100

80

418

79.4

100

84

422

 

 

HIGH

 

 

82.6/80.6

100/100

88/85

429

86.4/84.4

100/100

92/90

433

580J*16D

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

 

36.2

45

38

236

38.0

50

40

238

460--- 3--- 60

MED

0.25

1.8

37.2

50

39

245

39.0

50

41

247

 

HIGH

 

 

40.4

50

43

250

42.2

50

45

252

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STD

 

 

28.2

35

30

186

32.0

40

34

190

 

575--- 3--- 60

MED

0.24

3.8

28.2

35

30

186

32.0

40

34

190

 

 

HIGH

 

 

31.5

40

33

189

35.3

45

38

193

 

 

 

 

 

 

 

 

 

 

 

 

 

Legend and Notes for Table 1

LEGEND:

 

 

BRKR

---

Circuit breaker

CO

---

Convenience outlet

DISC

---

Disconnect

FLA

---

Full load amps

IFM

---

Indoor fan motor

LRA

---

Locked rotor amps

MCA

---

Minimum circuit amps

PE

---

Power exhaust

PWRD CO

---

Powered convenient outlet

UNPWR CO

---

Unpowered convenient outlet

NOTES:

 

 

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to de- termine the percentage of voltage imbalance.

max voltage deviation from average voltage

% Voltage Imbalance = 100 x

average voltage

Example: Supply voltage is 230-3-60

AB = 224 v

BC = 231 v

AC = 226 v

Average Voltage =

(224 + 231 + 226)

=

681

 

 

3

3

 

 

=227

Determine maximum deviation from average voltage. (AB) 227 – 224 = 3 v

(BC) 231 – 227 = 4 v (AC) 227 – 226 = 1 v Maximum deviation is 4 v.

Determine percent of voltage imbalance.

% Voltage Imbalance

= 100 x

4

 

227

 

 

 

= 1.76%

 

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

2011 Bryant Heating and Cooling Systems. D 7310 W. Morris St. D Indianapolis, IN 46231

Printed in U.S.A.

Edition Date: 01/11

Catalog No: SS580J---02

 

 

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Replaces: New