Section 3 — Maintenance

Bryant Air-cooled 7 kW, 12 kW and 15 kW Generators

MAINTENENANCE

Figure 3.1 – Generator Control Panel

Figure 3.3 — Oil Dipstick and Fill,

12 kW and 15 kW

OUTLET FUSE

 

EXTERNAL

 

GFCI

 

 

7.5A

 

CIRCUIT

MAN.

BREAKER

AUTO OFF

 

 

 

12 VDC

SYST

 

 

SET

 

 

EXERCISE

ACCESSORY

TIME

OUTLET 7.5A MAX

SYSTEM SET

LOW OIL

HIGH TEMP.

OVER SPEED

OVER CRANK

F L A S H I

 

N L E D =

N O

 

S E N S E

4 F L S H

R E

L E D S =

E X E R

R N O T S E T

Oil Dipstick

Oil Fill

3.2CHECKING THE ENGINE OIL LEVEL

For oil capacities, see “Specifications,” Section 1.5. For engine oil recommendations, see Section 3.3.1. To check the engine oil level, proceed as follows (Figures

3.2 and 3.3):

1.Start the generator by moving the AUTO/OFF/ MANUAL switch to the MANUAL position. Allow it to run for a short while and then shut it down by moving the switch to the OFF position.

2.Remove the dipstick and wipe it dry with a clean cloth.

3.Install the dipstick; then, remove it again. The oil level should be at the dipstick “Full” mark. If necessary, add oil to the “Full” mark only. DO NOT FILL ABOVE THE “FULL” MARK.

Never operate the engine with the oil level

!below the “Add” mark on the dipstick. Doing this could damage the engine.

4.Install the dipstick.

5.Reset the AUTO/OFF/MANUAL switch to its original position.

NOTE:

If the generator is to operate continuously for several days the oil level should be monitored frequently. A low oil shutdown can occur (Section 2.7.1) causing loss of generator power to emergency circuits.

Figure 3.2 — Oil Dipstick and Fill, 7 kW

Oil Dipstick and Fill

3.3CHANGING THE ENGINE OIL

‹3.3.1 ENGINE OIL RECOMMENDATIONS

Use oil of American Petroleum Institute (API) Service Class SG, SH or SJ. Use all season SAE 5W-30 Synthetic oil. Organic break-in oil is required before using synthetic oil.

NOTE:

The unit is supplied with organic “break-in” oil. See the “Break-in Procedure,” Section 2.1, for the first required oil change.

Any attempt to crank or start the engine before

!it has been properly serviced with the recommended oil may result in an engine failure.

‹3.3.2 OIL CHANGE PROCEDURE

To change the oil, proceed as follows:

1.Run the engine until it is thoroughly warmed up then shut OFF the engine.

2.Immediately after the engine shuts OFF, pull the oil drain hose (Figure 3.4) free of its retaining clip. Remove the cap from the hose and drain the oil into a suitable container.

3.After the oil has drained, replace the cap onto the end of the oil drain hose. Retain the hose in the clip.

4.Refill with the proper recommended oil (see Section 3.3.1). See Section 1.5.2 for oil capacities.

Bryant 13

Page 15
Image 15
Bryant ASPAS1BBA007 owner manual Checking the Engine OIL Level, Changing the Engine OIL, ‹ 3.3.1 Engine OIL Recommendations