CFM — Cubic Ft per Minute

EWB — Entering Wet Bulb ( °F)

LWB — Leaving Wet Bulb ( °F)

TC — Total Cooling Capacity 1000 Btuh

SHC — Total Sensible Capacity 1000 Btuh

BF — Bypass Factor

MBH — 1000 Btuh

NOTES:

1.Contact manufacturer for cooling capacities at conditions other than shown in table.

2.Formulas:

3.Direct interpolation is permissible. Do not extrapolate.

4.SHC is based on 80°F db temperature of air entering coil. Below 80°F db, subtract (Correction Factor x CFM) from SHC. Above 80°F db, add (Correction Factor x CFM) to SHC.

5.All data points are based on 10°F superheat leaving coil.

6.Bypass Factor = 0 indicates no psychometric solution. Use bypass factor of next lower EWB for approximation.

 

ENTERING AIR DRY BULB TEMPERATURE (°F)

 

 

 

 

 

 

 

 

79

78

77

76

75

Under 75

 

 

 

 

 

 

 

BYPASS

81

82

83

84

84

Over 85

 

 

 

 

 

 

 

 

 

 

 

 

Leaving db = entering db —

sensible heat cap.

1.09 x CFM

FACTOR

 

 

Correction Factor

 

0.10

0.98

1.96

2.94

3.92

4.91

Use formula

0.20

0.87

1.74

2.62

3.49

4.36

shown below

0.30

0.76

1.53

2.29

3.05

3.82

 

Leaving wb = wb corresponding to enthalpy of air leaving coil (hLWB)

total capacity (Btuh)

hLWB = hEWB —

4.5 x CFM

where hEWB = enthalpy of air entering coil.

Interpolation is permissible.

Correction Factor = 1.09 x (1 – BF) x (db – 80)

COIL STATIC PRESSURE DROP (In. WC)

UNIT SIZE

BULB

 

 

AIR QUANTITY (CFM)

 

 

 

 

 

 

 

 

 

 

 

 

600

700

800

900

—

—

A024

 

 

 

 

 

 

 

WET

0.08

0.10

0.13

0.16

—

—

 

 

DRY

0.06

0.08

0.11

0.13

—

—

 

 

 

 

 

 

 

 

 

 

700

800

900

1000

1100

—

A030

 

 

 

 

 

 

 

WET

0.08

0.12

0.15

0.19

0.23

—

 

 

DRY

0.08

0.10

0.14

0.17

0.21

—

 

 

 

 

 

 

 

 

 

 

900

1000

1100

1200

1300

—

A036

 

 

 

 

 

 

 

WET

0.16

0.19

0.23

0.27

0.32

—

 

 

DRY

0.13

0.17

0.21

0.25

0.29

—

 

 

 

 

 

 

 

 

 

 

1000

1100

1200

1300

1400

—

A042

 

 

 

 

 

 

 

WET

0.18

0.21

0.24

0.27

0.31

—

 

 

DRY

0.14

0.17

0.20

0.23

0.26

—

 

 

 

 

 

 

 

 

 

 

1300

1400

1500

1600

1700

—

A048

 

 

 

 

 

 

 

WET

0.19

0.22

0.25

0.28

0.31

—

 

 

DRY

0.18

0.21

0.24

0.27

0.30

—

 

 

 

 

 

 

 

 

 

 

1600

1700

1800

1900

2000

2100

A060

 

 

 

 

 

 

 

WET

0.19

0.22

0.24

0.26

0.28

0.30

 

 

DRY

0.18

0.20

0.21

0.24

0.26

0.28

 

 

 

 

 

 

 

 

—5—

Page 5
Image 5
Bryant CK3B manual Coil Static Pressure Drop In. WC, Entering AIR DRY Bulb Temperature F, Bypass, Factor