About Advanced Features & Operation

2 STAGE OPERATION - The 2nd Stage of heat or cool is turned on when (1) the 1st Stage has been on for a minimum of two minutes, and (2) the temperature spread from the setpoint is equal to or greater than: the setpoint plus the deadband, plus 2 degrees.

Heating

Cooling

2 degrees

Dead Band

Dead

Band

2 degrees

2nd Stage

1st Stage

Heat

Cool

1st Stage

2nd Stage

turn on

turn on

Setpoint

Setpoint

turn on

turn on

MINIMUM HEAT/COOL SETPOINT DIFFERENCE - The Heat and Cool setpoints will not be allowed to come any closer to each other than the value set in Advanced Setup step

#7, on page 13. This minimum difference is enforced during Auto changeover and Program On operation.