Burnham 101603-01R2-12/09 manual Maintenance

Models: 101603-01R2-12/09

1 8
Download 8 pages 20.62 Kb
Page 3
Image 3

WARNING

In the event that the ignition system on an ALP boiler does not permit the boiler to fire, there is either a problem with the ignition system or a problem with the vent system. Call a qualified gas service technician to diagnose and correct the problem.

A shutdown of the burner due to the pressure switch is an indication that there is a problem with the vent system, such as a blockage. The boiler pressure switch should only be reset after a qualified gas service technician has diagnosed and corrected the venting problem that caused the blocked vent air proving switch to open.

B. Maintenance

1.Safe reliable operation of this boiler depends upon proper periodic maintenance.

2.The following should be done on a continuous basis:

Keep the area around the boiler free of objects, which are flammable.

Do not store or use sources of hydrocarbons such as bleaches, fabric softeners, paints, cleaners, refrigerants, and cat boxes near the boiler. Traces of these chemicals can be drawn into the boiler, causing severe corrosion damage to the boiler and/or objectionable odors.

Do not expose the boiler to large amounts of dust such as that generated by dry wall construction or woodworking.

3.A qualified gas service technician should perform the maintenance procedure shown in the installation manual on an annual basis.

4.The owner should visually inspect the venting system on a monthly basis. If any of the following conditions are found, the boiler should be shut down and a qualified gas service technician called to correct the problem before the boiler is placed back in service:

Loose joints, corrosion or other deterioration

Condensate leakage

Sags in horizontal runs of vent pipe

5.The owner should also perform a monthly visual inspection of the boiler and the surrounding system piping. To do this, remove the boiler jacket door.

If any of the following are found, a qualified gas service technician should be consulted immediately:

Deterioration of the visible controls, wiring, and sheet metal components

Heating system water Leaks

Carbon (“soot”) in or near the burner compartment area

Make sure that the condensate drain system is unobstructed and leak tight.

CAUTION

The Alpine™ (ALP) has a heat exchanger made from a special stainless steel alloy which can be severely damaged by frequent additions of water or by the addition of boiler water additives which are not designed for use with stainless steel boilers. If it is necessary to add water to the boiler, have a service technician check the system for leaks. Do not add any chemicals to the boiler not listed in Section X of the Alpine™ (ALP) installation manual. Warranty is void if the service and maintenance procedure shown in Section XII of the Alpine™ (ALP) installation manual is not followed.

WARNING

Carbon (“soot”) in or near the burner compartment area is an indication of a potential carbon monoxide hazard. If carbon is found, the boiler should be shut down immediately and inspected by a qualified gas service technician. The cause of the sooting should be found and corrected before the boiler is restarted.

Page 3
Image 3
Burnham 101603-01R2-12/09 manual Maintenance