![](/images/new-backgrounds/1055709/557097x1.webp)
Ratings
Model |
| DOE |
|
|
|
|
|
|
|
|
|
|
| ||
Number | Input | Heating Capacity (MBH) | I=B=R Water Ratings |
|
|
| AFUE% |
|
|
| |||||
|
| ||||||
SCG3 / PVG3 | 70 | 60 | 52 | 85.5 | |||
SCG4 / PVG4 | 105 | 90 | 78 | 85.4 | |||
SCG5 / PVG5 | 140 | 120 | 104 | 85.3 | |||
SCG6 / PVG6 | 175 | 150 | 130 | 85.2 | |||
SCG7 / PVG7 | 210 | 179 | 156 | 85.0 | |||
SCG8 / PVG8 | 245 | 208 | 181 | 84.5* | |||
SCG9 / PVG9 | 280 | 238 | 207 | 84.0* |
*Only SCG3/PVG3 through SCG7/PVG7 are ENERGY STAR certified at 85+% AFUE
Specifications
Model | Dimensions (inches) | Connections (inches) | Water | Approximate | |||
Number | ‘A’ | ‘B’ | ‘C’ | Vent | Air Intake | Content (gal.) | Shipping Weight (lbs.) |
SCG3 / PVG3 | 11.65 | 26.60 | 38.09 | 3 | 3 | 2.16 | 210 |
SCG4 / PVG4 | 14.72 | 26.60 | 38.09 | 3 | 3 | 3.00 | 254 |
SCG5 / PVG5 | 17.78 | 26.60 | 38.09 | 3 | 4 | 3.84 | 298 |
SCG6 / PVG6 | 20.84 | 26.60 | 38.09 | 3 | 4 | 4.68 | 342 |
SCG7 / PVG7 | 23.90 | 26.60 | 38.09 | 3 | 5 | 5.52 | 386 |
SCG8 / PVG8 | 26.97 | 26.60 | 38.09 | 4 | 5 | 6.36 | 430 |
SCG9 / PVG9 | 30.03 | 26.60 | 38.09 | 4 | 5 | 7.20 | 474 |
(3/4” NPT)
SCG Model shown with vent connection
| © 2008 U.S. Boiler Company, Inc. - Lancaster, PA |
|
Form No. | Phone: |
|
www.burnham.com | Printed in the U.S.A. |