Burnham V8H Series manual I=B=R Net Ratings, Flue, Minimum Chimney Req, Afue %, Approx, Burner

Models: V8H Series

1 2
Download 2 pages 34.9 Kb
Page 2
Image 2
Ratings

(6)

Ratings

 

 

DOE

I=B=R Net Ratings

Flue

Minimum Chimney Req.

AFUE %

Approx.

 

Burner

Heating

 

 

 

Collar

 

 

 

 

 

Shipping

Boiler

Capacity

Capacity

Water

Steam

Steam

Dia.

Round

Rectangle

Height

 

 

Weight

Model

(GPH) (2)

(MBH) (3)

(MBH) (4)

(MBH) (5)

(Sq. Ft.)

(In) (8)

Dia.

In x In

Feet

Steam

Water

(Lbs)

V8H2 Water

0.60

70

61

5

6

8 x 8

15

82.1

450

V8H3 Steam

0.75

91

68

283

6

6

8 x 8

15

85.1

542

V8H3 Water

1.05

125

109

85.0

 

 

 

 

 

V8H4 Steam

1.05

127

95

396

6

6

8 x 8

15

85.3

634

V8H4 Water

1.35

162

141

7

85.3

 

 

 

 

V8H5 Steam

1.35

164

123

512

7

7

8 x 8

15

85.4

726

V8H5 Water

1.65

198

172

85.3

 

 

 

 

 

V8H6 Steam

1.65

201

151

629

7

7

8 x 8

15

85.7

818

V8H6 Water

1.90

228

198

8

85.3

 

 

 

 

V8H7 Steam

2.10

252

219

189

787

8

8

8 x 8

15

84.7

85.0

910

V8H7 Water

 

 

 

 

 

 

 

 

 

 

 

 

V8H8 Steam

2.35

275*

239

8

8

8 x 12

15

1002

V8H8 Water

2.35

266*

200

833

 

 

 

 

 

 

 

V8H9 Steam

2.60

299*

260

8

9

8 x 12

15

1094

V8H9 Water

2.60

298*

224

933

 

 

 

 

 

 

 

*I=B=R Gross Outputs

1.V8H2 is available as a packaged water boiler only and is not available with tankless heater.

2.The I=B=R Burner Capacity is based on oil having a heating value of 140,000 BTU/GAL.

3.DOE Heating Capacity and Annual Fuel Utilization Efficiency (AFUE) are based on U.S. Government tests at 13.0% CO2 with No. 1 maximum smoke and 0.02 inches water column over fire draft on standard equipment package.

4.Net I=B=R Ratings are based upon a pick-up allowance of 1.15. Consult manufacturer with unusual piping and pickup requirements before selecting boiler.

5.Net I=B=R Ratings are based upon a pick-up allowance of 1.333. Consult manufacturer with unusual piping and pickup requirements before selecting boiler.

6.As an ENERGY STAR® partner, Burnham has determined that those models with an AFUE of 85% and higher meet the ENERGY STAR® guidelines for energy efficiency.

7.Used for sizing flue connection materials. Maximum Working Pressure: 15 PSI steam; 30 PSI water, standard; 40 psi water optional; 50 psi water optional— USA only.

Boiler

 

 

 

Model

‘A’

‘B’

‘C’

V8H2

12-1/8”

6-5/8”

5”

V8H3

17-1/8”

9-1/8”

6”

V8H4

22-1/8”

11-5/8”

6”

V8H5

27-1/8”

14-1/8”

7”

V8H6

32-1/8”

16-5/8”

7”

V8H7

37-1/8”

19-1/8”

8”

V8H8

42-1/8”

21-5/8”

8”

V8H9

47-1/8”

24-1/8”

8”

FRONT VIEW

RIGHT SIDE VIEW

 

© 2007 U.S. Boiler Company, Inc. - Lancaster, PA

 

Form No. PL81401281000-11/07-10M

Phone: 1-888-432-8887

 

www.burnham.com

Printed in the U.S.A.

Page 2
Image 2
Burnham V8H Series I=B=R Net Ratings, Flue, Minimum Chimney Req, Afue %, Approx, Burner, Heating, Collar, Shipping