Cadet CEH-003PB, CEH-005P, CEH-005MB Wiring Diagrams, Control Voltage Wiring, Wiring Instructions

Models: CEH-005R CEH-005SB CEH-003RB CEH-003SB CEH-003MB CEH-003M CEH-003P CEH-003PB CEH-005PB CEH-003R CEH-005M CEH-005MB CEH-005P

1 8
Download 8 pages 63.99 Kb
Page 5
Image 5
Control Voltage Wiring

Wiring Instructions

Control Voltage Wiring

1.A knockout is also provided in the back of the unit for control wiring. This knockout is sized for 1/2" conduit. (see Figure 13)

2.Thermostat wire shall be as follows:

a.Line voltage control models: Use NEC Class 1, 600V, 90˚C, AWG #10 wire with copper conductor or same gauge wire as supply line.

b.24 volt control models (B package): Use NEC Class 1, 600V, 90˚C, AWG #18 wire with copper conductor.

Use H1 + P1, terminals for connection (Do not use jumpers).

3. Install wall thermostats in accordance with the installation instructions supplied with the thermostat.

NOTE: Do not locate thermostat in an area exposed to unusual temperature conditions or poor air circulation.

NOTE: a. Line voltage control models of 3.3KW and 5.0KW ratings that are 208 and 240 volt, wired for 3-phase operation, should not

be used with a wall thermostat. This applies to the following models:

CEH-003-M

CEH-003-P

CEH-005-M

CEH-005-P

These models come factory wired for single phase. When these models are converted in the field to 3-phase, DO NOT USE A WALL MOUNTED THERMOSTAT. Thermostat control for 3-phase hookup should be provided by a CEK-TB2 (built-in thermostat).

b.When using model number CEH-005-M wired single phase (factory wired) use the following thermostats: Wall Mount – C611-25,

Built-InCEK-TB2 (two-stage thermostat)

4.Connect the thermostat wires to terminals H1 and P1 as shown in Figure 13. On 208 and 240 volt, single-phase models with line voltage control, (Not B package models) install jumpers as shown in Figure 13.

BACK

FRONT

Figure 14.

Manual reset limit

 

Heater Elements

 

A manual reset thermal limit is

 

 

 

 

 

Line Voltage

factory installed on all models.

FRONT

 

 

 

 

Control Models

The limit is located on the front of

 

To Thermostat

H1

H2

F2

(Singe Phase):

the heater. The manual reset limit

 

Install jumpers

 

 

 

 

 

will not reset until the button is

 

 

 

 

 

between H1 and H2

pushed and heater has cooled

 

 

P1

P2

F1

and P1 and P2 on

down. (208/240V line voltage con-

Manual Reset Limit

 

 

208/240V units

trol heaters use two manual reset

Connect Thermostat

Control Terminal Board

(note dashed lines).

 

limits)

 

Wires To P1 and H1

 

 

 

 

 

 

 

 

Figure 13. Thermostat wiring connections

Wiring Diagrams

5

Page 5
Image 5
Cadet CEH-003PB, CEH-005MB, CEH-003R, CEH-005PB, CEH-003M Wiring Diagrams, Control Voltage Wiring, Wiring Instructions