72
APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE ITEM DISPLAY ITEM DESCRIPTION COMMENT
M.MST
MOTORMASTER
MMR.S YES/NO Motormaster Select
P.GAN XX Head Pressure P Gain Default: 1
Range: 1 to 4
I.GAN XX.X Head Pressure I Gain Default: 0.1
Range: -20 to 20
D.GAN XX.X Head Pressure D Gain Default: 0.0
Range: -20 to 20
MIN.S XX Minimum Fan Speed
RSET
RESET COOL TEMP
CRST X Cooling Reset Type
Default: 0
0 = No Reset
1 = 4 to 20 mA Input
2 = Outdoor Air Temperature
3 = Return Temperature
4 = Space Temperature
MA.DG XX.XΔF4-20 - Degrees Reset Default: 0.0 ΔF
Range: -30 to 30 ΔF
RM.NO XXX.X °F Remote - No Reset Temp Default: 125 F
Range: 0º to125 F
RM.F XXX.X °F Remote - Full Reset Temp Default: 0 F
Range: 0º to125 F
RM.DG XX.X °F Remote - Degrees Reset Default: 0.0 ΔF
Range: -30 to 30 ΔF
RT.NO XXX.XΔFReturn - No Reset Temp Default: 10.0 ΔF
Range: 0º to125 F
RT.F XXX.XΔFReturn - Full Reset Temp Default: 0 ΔF
Range: 0º to125 F
RT.DG XX.X °F Return - Degrees Reset Default: 0.0 ΔF
Range: -30 to 30 ΔF
DMDC X Demand Limit Select
Default: 0
0 = None
1 = Switch
2 - 4 to 20 mA Input
3 = CCN Loadshed
DM20 XXX% Demand Limit at 20 mA Default: 100%
Range: 0 to 100%
SHNM XXX Loadshed Group Number Default: 0
Range: 0 to 99
SHDL XXX% Loadshed Demand Delta Default: 0%
Range: 0 to 60%
SHTM XXX Maximum Loadshed Time Default: 60 minutes
Range: 0 to 120 minutes
DLS1 XXX% Demand Limit Switch 1 Default: 80%
Range: 0 to 100%
DLS2 XXX% Demand Limit Switch 2 Default: 50%
Range: 0 to 100%
SLCT
SETPOINT AND RAMP LOAD
RL.S ENBL/DSBL Ramp Load Select Default: Enable
CRMP ENBL/DSBL Cooling Ramp Loading Default: 1.0
Range: 0.3 to 2
SCHD XX Schedule Number Default: 1
Range: 1 to 99
Z.GN X.X Deadband Multiplier Default: 1
Range: 1 to 4
SERV
SERVICE CONFIGURATION
EN.A1 YES/NO Enable Compressor A1
EN.A2 YES/NO Enable Compressor A2
EN.A3 YES/NO Enable Compressor A3
EN.B1 YES/NO Enable Compressor B1
EN.B2 YES/NO Enable Compressor B2
EN.B3 YES/NO Enable Compressor B3
EN.FB YES/NO Enable Compressor FBack
REV.R YES/NO Reverse Rotation Enable
BCST
BROADCAST CONFIGURATION
T.D.B ON/OFF CCN Time/Date Broadcast
OAT.B ON/OFF CCN OAT Broadcast
G.S.B ON/OFF Global Schedule Broadcst
BC.AK ON/OFF CCN Broadcast Ack'er