NOTE:
AVOID CONTACT BETWEEN TUBING AND STRUCTURE
INDOOR WALL
OUTDOOR WALL
CAULK
INSULATION
THROUGH THE WALL | VAPOR LINE | ||
|
|
| LIQUID LINE |
|
|
|
INSTALL SOLENOID VALVE IN LIQUID TUBE
Solenoid valve must be energized during evacuation for effective evacuation.
Before making liquid tube connections, install
If a
HANGER STRAP (AROUND VAPOR LINE ONLY)
INSULATION
SUSPENSION
JOIST
VAPOR LINE
1″ |
|
| LIQUID |
MIN |
|
| |
|
| LINE | |
|
|
| |
|
|
| A92469 |
1.Remove coil liquid connection cap and discard.
2.Mount solenoid valve on liquid tube, making sure valve flow arrow points toward indoor coil. Mount valve in any position except valve body at top and electric coil at bottom. (See Fig. 4.) The solenoid valve is to be installed a maximum of 24 in. from indoor coil.
3.Braze valve onto end of liquid tube using silver bearing or
4.Braze flare adapter onto outlet end of the solenoid valve.
5.Wire solenoid coil into system control circuit as shown in Fig. 6.
Table 1ÐRefrigerant Connections and Recom- mended Liquid and Vapor Tube Diameters (In.)
UNIT | LIQUID | VAPOR | |||
Connect | Tube | Connect | Tube | ||
SIZE | |||||
Diameter | Diameter | Diameter | Diameter | ||
| |||||
018, 024 | 3/8 | 3/8 | 5/8 | 5/8 |
Fig. 3ÐPiping Installation
ELECTRICAL JUNCTION
ELECTRICAL COIL
VALVE
FLOW ARROW
STRAIGHT 3/8 IN. STUD
NOTE: System flow direction must match arrow on bottom of body.
Fig. 4ÐSolenoid Valve Installation
A87044
connected by 15 ft of
030, 036 | 3/8 | 3/8 | 3/4 | 3/4 |
042, 048 | 3/8 | 3/8 | 7/8 | 7/8 |
060 | 3/8 | 3/8 | 7/8 |
Notes: 1. Tube diameters are for lengths up to 50 ft. For tubing lengths greater than 50 ft, consult
2. Do not apply capillary-tube indoor coils to these units.
REFRIGERANT TUBING Ð Connect tubing to fittings on out- door unit vapor and liquid service valves. (See Fig. 2.)
A brazing shield MUST be used when tubing sets are being brazed to the service valves to prevent damage to the painted unit surface.
Relieve pressure and recover all refrigerant before system repair or final unit disposal to avoid personal injury or death. Use all service ports and open all flow control devices, including solenoid valves.
To avoid valve damage while brazing, service valves must be wrapped with a
SWEAT CONNECTION Ð Use refrigerant grade tubing. Service valves are closed from factory and ready for brazing. After wrapping the service valve with a wet cloth, the tubing set can be brazed to the service valve using either silver bearing or
3