Step 14 — Install Humidistat for Optional

MoistureMi$er™ Package — MoistureMi$er dehu-
midification package operation can be controlled by field
installation of a Carrier-approved humidistat. To install the
humidistat perform the following procedure:
1. Locate humidistat on a solid interior wall in the condi-
tioned space. Location should be a well ventilated area
to sense average humidity.
2. Route thermostat cable or equivalent single leads of col-
ored wire from Humidistat terminals through conduit in
unit to the low voltage connection on the 2-pole terminal
strip (TB3) as shown in Fig. 44 and Fig. 45. See Fig. 46
for operational diagram.
Fig. 45 — Typical MoistureMi$er Dehumidification
Package Control Box
Fig. 44 — Typical MoistureMi$er Dehumidification Package
Humidistat Wiring Schematic (460 V Unit Shown)