TROUBLESHOOTING

See Fig. 7-10 for Apollo factory, control, and system wiring.

Blank Display or Blinking Display at the Thermostat

1.Check to ensure there is at least 20.5 vac across the 2 termi- nals labelled 24 vac. If there is not at least 20.5 vac, check the unit transformer which is powering the Apollo control.

2.If an ac voltage between 20.5 and 30 vac is read, check for 10 vdc between the terminals labelled WHT and RED. If there is 0 vdc between the terminals, replace the Apollo control. If a value between 1 and 10 vdc is read, check the wiring between the thermostat and the Apollo control.

3.If the thermostat display is blinking on and off, this is an indication that there is a communication problem be- tween the thermostat and the Apollo control. The thermo- stat and the Apollo control communicate on the blue and yellow wires. If either one is shorted, open, or crossed, it will cause the thermostat display to blink.

To check the wiring between the thermostat and the Apollo control:

1.Remove the thermostat and connector board.

2.Wire the connector board to the Apollo control with a short piece of field-supplied 5-conductor cable.

3.Plug the thermostat into the connector board.

a.If thermostat powers up, there is a wiring problem. Find the open or shorted wire, or replace the wiring between the thermostat and the Apollo control.

b.If the thermostat does not power up, try another thermostat. If the new thermostat powers up, replace the off thermostat. If the new thermostat will not power up, replace the Apollo control.

The Control Will Not Energize Heating

1.The thermostat is not displaying the heat indicator:

a.Check the heating lockout temperature set point and options to make sure the outdoor-air tempera- ture is locking out Heating mode.

b.Ensure that a sensor in the system is not reading above the heating high limit temperature. If a sup- ply air sensor or a direct expansion (DX) coil sen- sor is not connected to the Apollo control, turn off the High and Low Limits option at the thermostat.

c.Check the Heat switch and make sure it is in the AUTO. position.

2.The thermostat is displaying the heat indicator.

a.Check to see if the H1 LED (light-emitting diode) is lit on the Apollo control. If it is not, replace the Apollo control. If the H1 LED is lit on the Apollo control, check the voltage across the H1 relay con- tact. If it reads 24 vac, replace the Apollo control. If it reads 0 to 2 vac, check the H1 contactor and the unit transformer.

The Control Will Not Energize Second Stage Heating

1.The thermostat is not displaying the second stage indica- tor. A decimal point on the thermostat display screen is the indication that the thermostat is asking for second stage.

a.Check to see if the space demand is equal to or greater than 2° F. The control must see a 2° F demand before it will call for second stage.

b.Check the Temperature Trend Staging option. If this option is configured to “on” and space condi- tions are improving, the control will not energize the second stage.

2.The thermostat is displaying the decimal point.

a.Check to see if the H2 LED is lit on the Apollo control. If it is not lit, replace the Apollo control.

b.The LED is lit, but second stage is not energized. Check the voltage across the H2 relay contact. If it reads 24 vac, replace the relay board. If it reads 0 to 2 vac, check the H2 contactor and the unit transformer.

The Control Will Not Energize Cooling

1.The thermostat is not displaying the cool indicator.

a.Check the cooling lockout temperature set point and options to make sure the outdoor-air tempera- ture is not locking out Cooling mode.

b.Ensure that a sensor in the system is not reading below the cooling low limit temperature. If a sup- ply air sensor or a direct expansion (DX) coil sen- sor is not connected to the relay pack, turn off High and Low Limits at the thermostat.

c.Check the Cool switch and make sure it is in the AUTO. position.

2.The thermostat is displaying the cool indicator.

a.Check to see if the C1 LED is lit on the Apollo con- trol. If it is not, replace the Apollo control. If the C1 LED is lit on the Apollo control, check the voltage across the C1 relay contact. If it reads 24 vac, replace the Apollo control. If it reads 0 to 2 vac, check the C1 contactor and the unit transformer.

The Control Will Not Energize Second Stage Cooling

1.The thermostat is not displaying the second stage indica- tor. A decimal point on the thermostat display screen is the indication that the thermostat is asking for second stage.

a.Check to see if the space demand is equal to or greater than 2° F. The control must see a 2° F demand before it will call for second stage.

b.Check the Temperature Trend Staging option. If this option is configured to “on” and space condi- tions are improving, the control will not energize the second stage.

2.The thermostat is displaying the decimal point.

a.Check to see if the C2 LED is lit on the Apollo control. If it is not lit, replace the Apollo control.

b.The LED is lit, but second stage is not energized. Check the voltage across the C2 relay contact. If it reads 24 vac, replace the relay board. If it reads 0 to 2 vac, check the C2 contactor and the unit transformer.

The Control Will Not Energize The Fan

1.The fan indicator is not lit on the thermostat.

a.The Fan switch is in the AUTO. position and the control is not in a mode (HEAT or COOL position).

b.The fan switch is in the ON position but the ther- mostat is in setback and has no mode.

c.The thermostat has just received power or has just reset and is going through its initialization process.

2.The fan indicator is lit on the thermostat.

a.Check the fan LED on the Apollo control. If it is not lit, replace the Apollo control.

b.If the fan LED is lit, check the voltage across the fan relay contact. If it reads 24-vac, replace the relay board. If it reads 0 to 2 vac, check the fan contactor and the unit transformer.

5

Page 5
Image 5
Carrier TM004-014, 50HJQ004-016, 48/50TF, 50TFQ004-012, 48/50HJ004-024, TM016-028, 48/50TJ specifications Troubleshooting

TM004-014, TM016-028, 48/50TF, 50HJQ004-016, 48/50TJ specifications

Carrier has long been a leader in the heating, ventilation, and air conditioning (HVAC) industry, and their line of rooftop units, including the models 50TFQ004-012, 48/50HJ004-024, 48/50TJ, 50HJQ004-016, and 48/50TF, exemplifies their commitment to innovation and efficiency. These units are designed to meet the diverse needs of commercial buildings while providing precise climate control, reliability, and efficiency.

One of the main features of these rooftop units is their advanced cooling and heating capabilities. The units are equipped with high-efficiency scroll compressors that enhance performance and reduce energy consumption. This technology allows these units to operate efficiently even under varying load conditions, making them ideal for buildings with fluctuating occupancy levels.

In addition to their efficient compressors, Carrier rooftop units utilize variable speed fans, which help optimize airflow and further improve energy efficiency. The variable speed technology adjusts the fan speed to match the cooling or heating demand, ensuring a consistent and comfortable indoor environment. This adaptability not only enhances user comfort but also significantly reduces operational costs.

Another key characteristic of the 50TFQ004-012 and similar models is their compact design, making them suitable for a variety of rooftop spaces. These units are built with robust materials to endure harsh weather conditions, ensuring durability and long-lasting performance. Their lightweight construction also simplifies the installation process, allowing for faster project completion.

Furthermore, the models in this line come equipped with user-friendly control systems. These systems provide intuitive management and monitoring capabilities, allowing building operators to easily adjust settings and schedules. This feature ensures that energy consumption is kept to a minimum while maintaining optimal comfort levels.

Finally, Carrier incorporates advanced diagnostic features in these rooftop units, enabling proactive maintenance and reducing downtime. Through real-time monitoring, any potential issues can be addressed before they become significant problems.

In conclusion, Carrier's 50TFQ004-012, 48/50HJ004-024, 48/50TJ, 50HJQ004-016, and 48/50TF rooftop units blend powerful performance with cutting-edge technology. Their energy-efficient design, reliable components, and advanced control systems make them an excellent choice for any commercial HVAC application, ensuring a comfortable and cost-effective indoor environment.