Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). * Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 12° C (10° F) above 15.5° C (60°F).
Engine Start Sequence
-Manual/Test (start) ......................................................................................................................
-Off ............................................................................................................................................
Automatic Start on Utility failure
7 day exerciser
Stops unit. Power is removed Control and charger still operate Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Cyclic cranking: 7 sec. on, 7 rest
(90 sec. maximum duration)
Engine Warm-up ..................................................................................................................................................... 10 seconds
Engine Cool-Down ..................................................................................................................................................... 1 minute
Starter Lock-out ........................................................................................................................................ Starter cannot re-engage until
5 sec. after engine has stopped.
2.5 Amp Timed Trickle Battery Charger .................................................................................................................. Standard
Automatic Voltage Regulator w/Overvoltage Protection ............................................................................................ Standard
Automatic Low Oil Pressure Shutdown ..................................................................................................................... Standard
Overspeed Shutdown ............................................................................................................................................ Standard, 72Hz
High Temperature Shutdown ..................................................................................................................................... Standard
Overcrank Protection ................................................................................................................................................. Standard
Safety Fuse ............................................................................................................................................................... Standard
Mode Switch
-Auto ...............................................................................................................................................
Required fuel pressure to generator fuel inlet at all load ranges - 5 to 7 inches of water column for natural gas, 10 to 12 inches of water column for LP gas
CONTROLS
Home Standby - 16kW | |
GENERATOR | Model ASPBS1CCA016 - Steel, Model ASPBA1CCA016 - Aluminum |
Rated Maximum Continuous Power Capacity (LP) | 16,000 Watts* |
Rated Maximum Continuous Power Capacity (NG) | 15,000 Watts* |
Rated Voltage | 120/240 |
Rated Maximum Continuous Load Current | |
120 Volts | 133.3 LP/125 NG |
240 Volts | 66.6 LP/62.5 NG |
Main Line Circuit Breaker | 65 Amp |
Phase | 1 |
Number of Rotor Poles | 2 |
Rated AC Frequency | 60Hz |
Power Factor | 1 |
Battery Requirement (not included) | Group 26, 12 Volt Netgative Ground and 525 Cold-cranking Amperes Minimum |
Unit Weight | 445 lbs. (Steel), 414 lbs. (Alum) |
Dimensions (L” x W” x H”) | 48 x 24 x 28-1/4 |
Sound output in dB(A) at 23 ft. with generator operating at full load | 71.5 |
Sound output in dB(A) at 23 ft. with generator in Ultra Quiet exercise mode | 59 |
ENGINE | Model ASPBS1CCA016 - Steel, Model ASPBA1CCA016 - Aluminum |
Type of Engine | OHVI V-TWIN |
Number of Cylinders | 2 |
Rated Horsepower | 30 @ 3,600 rpm |
Displacement | 992cc |
Cylinder Block | Aluminum w/Cast Iron Sleeve |
Valve Arrangement | Overhead Valve |
Ignition System | Solid-state w/Magneto |
Governor System | Electronic |
Compression Ratio | 9.5:1 |
Starter | 12Vdc |
Oil Capacity Including Filter | Approx. 1.7 Qts. |
Standby Operating RPM | 3,600 |
Exercise RPM | 2400 |
Fuel Consumption | |
Natural Gas cu.ft./hr. | |
........................................1/2 Load | 173 |
........................................Full Load | 245 |
Liquid Propane ft3/hr (gal/hr) | |
........................................1/2 Load | 59 (1.59) |
........................................Full Load | 92 (2.51) |