2
Table1—Kit Usage and Cut In/CutOut Pressures
KITPARTNO. REFRIGERANT PRESSURE SWITCH C LOSES
(PSIG)
PRESSURE SWITCH OPENS
(PSIG)
WIRECOLORS
KSALA0201R22 R--- 22 225 100 Blue and Yellow
KSALA0301410 R---410A 365 200 Blueand Violet
SERVICE FITTING CAP
VALVE CORE END
ADAPTER TEE
FLARE NUT
ON PRESSURE
SWITCH
LIQUID REFRIGERANT SERVICE
VALVE SERVICE FITTING
EXTENDER TUBE
FLARE NUT
A00025
Fig.1 Low--AmbientPressureSwitch
REQUIRED CHANGES FOR COOLING UNITS AND
HEATPUMP UNITS
1. Crankcase heaters are required on all app lications where
low--ambient controls are used.
2. Start capacitor and relay (hard start) kits are required on all
single--phase applications wherelow--ambientcontrols are
used.
3. Evaporator freeze thermostat KAAFT0101AAA is
required on allapplications where low--ambientcontrols
areu sed.
4. Wind bafflesare required for temperaturesbelow 0_For
wherethere is substantialwind.
NOTE: When wind bafflesare used, raising unit offof pad a
minimum of 4 in. is required to provide better airflow for
moderate-- and high--ambient temperatures. Check pre--sale
literature for available support feetor unit risers.
CUTHAZARD
Failure to follow this caution could result in personal
injury.
Toreduce risk of personalinjury, wearpersonal protective
equipment when working with wind baffles. Only
experiencedtechnicians should fabricateand install wind
baffles.

!

CAUTION
5. For cooling applications only, winter start control
KAAWS0101AAA must be used where low--pressure
switchtripping may be encountered. Winterstart control
must be wired in parallel with low--pressure switch. This
allows a delay of 3 minu tes before low--pressure switch
becomes part of control circuit. (See Fig. 5 .)
CONNECTOR
CONTACTOR
BLUE
BLACK
FAN
MOTOR
PRESSURE
SWITCH
YELLOW
OR
VIOLET
A97326
Fig.2 Power Wiringfor All Voltages of
Cooling Applications
DEFROST
BOARD
OF2
O
C
ISOLATION
RELAY
YELLOW
OR VIOLET
BLUE
BLACK
FAN
MOTOR
PRESSURE
SWITCH
A97327
Fig.3 Power Wiringfor 208/230v Heat Pump
Applications
DEFROST
BOARD
O
C
ISOLATION
RELAY
YELLOW
OR VIOLET
BLUE
OUTDOOR
FAN RELAY
BLACK
FAN
MOTOR
PRESSURE
SWITCH
13
A97328
Fig.4 Power Wiringfor 460v Heat Pump Applications
KSALA