Fig. 1 — Heat Section Details

LIMIT

SWITCH

NO. 2

FLUE OUTLET

SECTION 2

GAS VALVE

FLUE

OUTLET

SECTION 1

GAS VALVE

LIMIT

SWITCH

NO. 1

NOTE: High heat consists of sections 1 and 2. Low heat consists of section 1 only.

030-050 SIZES

LIMIT

SWITCH

NO. 1

FLUE

FLUEOUTLET OUTLET

SECTION 2

SECTION 1

GAS VALVE

GAS VALVE

LIMIT

SWITCH a48-8445a

NO. 2

NOTE: High heat consists of sections 1-3. Low heat consists of sections 1 and 2 only.

055-100 SIZES LOW HEAT

 

Fig. 1 — Heat Section Details

a48-8445a

a48-8445b

LIMIT

SWITCH

NO. 1

FLUE

OUTLET

SECTION 2

GAS VALVE

FLUE

FLUEOUTLET OUTLET

SECTION 3

SECTION 1

GAS VALVE

GAS VALVE

 

LIMIT

SWITCH

NO. 2

10.Using the scrolling marquee, enable the unit to run using the following procedure:

a.Push the ESCAPE key unit a blank display screen is shown.

b.Push the a48-8445b key until the SERVICE TEST LED is lit.

c.Push the ENTER key. The display will show STOP.

d.Push the ENTER key again. The NO/YES display will flash.

e.Push the Fig. 1 — Heat Section Details (cont)a48-8446Manual background or Manual background key to toggle the display to NO

and then push ENTER . The unit will return to

normal operation and exit SERVICE TEST mode.

11.To test the operation of the gas section, use the scrolling marquee Service Test routine to energize the gas outputs and to turn on the gas. Refer to the unit Controls, Start- Up, Operation, Service and Troubleshooting literature for more information.

12.For normal operation, make sure that units with a conven- tional thermostat are set to heating control temperature. On VAV (variable air volume) and constant volume units with a space temperature sensor, make sure that the set points are at the normal heat set points.

NOTE: High heat consists of sections 1-3. Low heat consists of sections 1 and 2 only.

055-100 SIZES HIGH HEAT

Fig. 1 — Heat Section Details (cont)

a48-8446

Manual background WARNING

If the main burners fail to light or the blower fails to start, shut down gas heating section and call your dealer for ser- vice. Failure to follow these requirements could result in serious personal injury.