TB-- NAC / TB-- NHP

SClose to or in direct airflow from supply registers and return-air grilles.

SIn areas with poor air circulation, such as behind a door or in an alcove.

Step 2 — Install Thermostat

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Before installing thermostat, turn off all power to unit. There may be more than 1 disconnect.

1.Turn OFF all power to unit.

2.If an existing thermostat is being replaced:

a.Remove existing thermostat from wall.

b.Disconnect wires from existing thermostat, one at a time. Be careful not to allow wires to fall back into wall.

c.As each wire is disconnected, record wire color and terminal marking.

d.Discard or recycle old thermostat.

!CAUTION

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmental damage.

Mercury is a hazardous waste. Federal regulations require that Mercury be disposed of properly.

3.Separate front and back (mounting base) assembly of thermostat.

4.Route thermostat wires through hole in mounting base. Level mounting base against wall (for aesthetic value only, thermostat need not be level for proper operation) and mark wall through 2 mounting holes.

5.Drill two 3/16-in. mounting holes in wall where marked.

6.Secure mounting base to wall with 2 anchors and screws provided making sure all wires extend through hole in plastic.

7.Strip 1/4 in. insulation from thermostat wire and adjust length to reach terminal block connector on mounting base. Match and connect proper wiring in accordance with wiring diagrams.

8.Push any excess wire back into wall. Seal hole in wall to prevent air leaks. Leaks can affect thermostat operation. Any excess wire left inside thermostat casing may also affect thermostat operation by interfering with airflow across the temperature sensor.

9.Snap thermostat together making sure terminal block connector aligns, and assembly is secure.

10.Turn on power to unit.

On power up, depending on the thermostat model being used, the LCD readout will display either, AC or PC for air conditioner model (1-stage heat/1-stage cool), or HP or PH for heat pump model (2-stage heat/1-stage cool).

Step 3 — Set Thermostat Configuration

Configuration options allow the installer to configure the thermostat for a particular installation. These selections are

intended to be made at installation and normally are not modified by the homeowner. Below is a list of available options followed by a description of each one.

Option 01 - Equipment Type

Option 03 - Fahrenheit or Centigrade operation Option 04 - Enable fan (G) ON with heat (W)

Option 10 - O (reversing valve) On with Heat or Cool (present on Heat Pump model only)

Option 13 - Room temperature offset adjustment

Note that not all configuration option numbers are used in this product.

To Enter The Configuration Mode:

Press and hold FAN button for approximately 10 sec until room temperature disappears and the display reads “01”. You are now in configuration mode.

NOTE: If FAN button is pressed again, or if no button is pressed for 2 minutes, the thermostat will exit configuration mode and return to normal operation. To re-enter configuration mode, the FAN button must be pressed and held for 10 sec again.

While in the configuration mode, the temperature display is used to show both the option number and the selected choice within each option. Each press of the H/C button alternates between the option number and the selection within that option. When the configuration mode is first entered, option 01 is displayed. The up and down buttons now move between the available option numbers. Once an option number is selected, press the H/C button once to display the currently selected choice within that option. The up and down buttons now move between the available choices within that option. After the new choice is made, press the H/C button again to return to the option number display. When finished with option selections, press FAN button once to exit the configuration mode.

Option 01 — Equipment Type

Selections: with HP thermostat: HP, AC, PH, or PC with AC thermostat: AC or PC

Meanings:

PH or PC selects PTAC units (Packaged Terminal Air Conditioners) which are used in motel rooms and other rented spaces. When this option is selected, the display shows only the setpoint, not the room temperature. Also the compressor timeguard is disabled, allowing the compressor to turn on immediately when a demand is established.

HP or PH controls 1 speed heat pump with 1 stage of aux heat. AC or PC controls 1 speed air conditioner with one stage of heat.

Note that this option allows a HP thermostat to be converted to control an AC system.

Option 03 — Fahrenheit/Centigrade Selection

This selection operates the thermostat in either Fahrenheit or Centigrade. Factory default is F.

Available Selection:

Use UP and DOWN buttons to change between F and C.

Option 04 — G (fan) ON with W (Heat) Selection

This selection determines whether G (fan) output is to be ON or OFF when W (furnace or strip heat) output is ON. Most furnaces and fan coils manage their own blowers and do not require a separate G signal. For these applications, select OFF. Some auxiliary heaters require a separate G signal from the thermostat to turn on the blower. In this case, select ON. Factory default is OF (off).

Available Selection:

Use UP and DOWN buttons to change between ON and OFF.

2

Page 2
Image 2
Carrier TB-NAC, TB-NHP installation instructions Install Thermostat, Set Thermostat Configuration, Option 01 Equipment Type

TB-NAC, TB-NHP specifications

Carrier TB-NHP and TB-NAC units are advanced commercial air conditioning systems designed to deliver exceptional comfort and efficiency in a variety of environments. These models exemplify Carrier's commitment to innovation, performance, and sustainability in HVAC technology.

The TB-NHP model is specifically engineered for high-performance needs, making it ideal for large commercial spaces. One of its standout features is the advanced inverter technology which enables the unit to adjust its cooling capacity based on real-time demand. This not only enhances energy efficiency but also provides consistent temperature control, ensuring a comfortable indoor environment.

In contrast, the TB-NAC model excels in providing precise temperature control and energy savings for smaller spaces. This model incorporates a powerful, compact design suited for environments where space is a premium. The TB-NAC utilizes scroll compressor technology, leading to quieter operation and improved efficiency, making it ideal for residential buildings or small commercial applications.

Both models feature Carrier's innovative EcoWise refrigerants that not only comply with global environmental standards but also support the reduction of greenhouse gas emissions. This is particularly important in today's climate-conscious marketplace where sustainability is a key consideration for building owners and operators.

Reliability is another hallmark of the TB-NHP and TB-NAC series. Engineered with rugged components and tested to withstand harsh environments, these units promise longevity and reduced maintenance costs. They are also equipped with smart controls that can be integrated into building management systems, allowing for remote monitoring and diagnostics, which facilitate proactive maintenance and enhance operational efficiency.

The TB-NHP and TB-NAC units are not only valued for their advanced technology and reliability but also for their quiet operation. Low noise levels ensure that these air conditioning systems do not disrupt the working or living environment, making them a preferred choice in noise-sensitive areas.

In summary, Carrier's TB-NHP and TB-NAC models stand out in the HVAC market due to their cutting-edge technology, energy efficiency, and durability. These systems are a testament to Carrier's dedication to providing innovative solutions that meet the complexities of modern commercial and residential climate control needs.