→OPERATIONAL INFORMATION
This timer prevents the compressor from starting unless it has been off for at least 5 minutes. It can be defeated for 1 cycle by simultaneously pressing the FAN mode button and the INCREASE TEMPERATURE button.
This timer prevents the start of a heating or cooling cycle until at least 15 minutes after the last start of the same cycle. Its function is to assure that equipment is not cycled more than 4 times per hour. This timer is defeated for 1 cycle when the desired temperature is manually changed. It can also be defeated for 1 cycle by simultaneously pressing the FAN mode button and the INCREASE TEMPERATURE button.
In multistage heating or cooling, this timer prevents any higher stage from turning on until the preceding stage has been on for 15 minutes. This timer is defeated if the temperature error is greater than 5ÊF (usually due to a large change in desired temperature).
In normal operation, when a stage turns on, it will not turn off for a minimum of 3 minutes.
Heat/Cool Set Points (Desired Temperatures)
A minimum difference of 2 degrees is enforced between heating and cooling set points. This is done by allowing one setting to "push" the other, to maintain this difference.
Auto Changeover
When the auto changeover mode is selected, a change from heat to cool (or vice versa) will not occur until an opposite mode demand has existed for 20 minutes. If the setpoint is changed, the 20 minute requirement is deleted.
Emergency Heat Mode
When thermostat is configured as a heat pump and emergency heat mode is selected, all Y signals are locked out and W becomes energized upon a call for heat.
Power On Check
When AC power is first applied, all segments of the display are turned on for a few seconds. Following this, the temperature display indicates the model/configuration via the following 2 digit code:
Error Codes
--Ð If the thermostat cannot properly read room temperature, the display will indicate
E2 Ð If the AC line voltage drops below a minimum (brownout) level, all outputs are turned off and the display indicates E2. This condition will remain for 15 seconds after proper line voltage is restored. If the AC line voltage disappears completely, the display will immediately go blank.
E3 Ð If thermostat cannot properly read outdoor temperature, and/or it is needed for proper operation, (i.e. Option 8 is ON with no sensor attached), E3 will alternate with room temperature on the room temperature display and the outdoor temperature will read
Outdoor Temperature
When an outdoor temperature sensor is attached, outdoor temperature can be read by pressing up and down buttons together. While it is displayed, the letters "od" also appear in the heat set point display.
Smart Recovery
With Smart Recovery selected, the transition out of a heating setback begins 90 minutes early, gradually adjusting room temperature so that the desired temperature will be achieved at the selected time.
→Thermostat Troubleshooting
SYMPTOM | WHAT TO CHECK | |
|
| |
| Temperature sensor reading out of range. Check sensor for damage. If recycyling power | |
does not clear display, thermostat should be replaced. | ||
| ||
|
| |
"E2" on temperature display | Brownout condition or too low of voltage to thermostat. Double check wiring and check for | |
24 VAC between R and C. E2 will clear 15 seconds after proper voltage is restored. | ||
| ||
|
| |
"E3" on temperature display | Outdoor temperature reading out of range and needed for Option 8. Check outdoor tem- | |
perature sensor and its wiring. | ||
| ||
"Clean Filter" on temperature display | After the selected number of hours of blower operation "clean filter" will display on LCD. | |
This is to remind the homeowner to "check" filter. Press "reset filter" button to clear dis- | ||
| play and reset timer to 0. | |
|
| |
| Select COOL mode. Decrease cooling setpoint to 10 degrees below room temperature. | |
Cooling will not come on | Simultaneously press FAN and INCREASE TEMPERATURE buttons to defeat timers. | |
Check for 24 VAC at Y/Y2 terminal. If present, thermostat is OK and problem is with | ||
| ||
| equipment or wiring. If not present, replace thermostat. | |
| Select HEAT mode. Increase heating setpoint to 10 degrees above room temperature. | |
Heating will not come on | Simultaneously press FAN and INCREASE TEMPERATURE buttons to defeat timers. | |
Check for 24 VAC at Y/Y2 (with HP) or W/W1 (with AC) terminal. If present, thermostat is | ||
| ||
| OK and problem is with equipment or wiring. If not present, replace thermostat. | |
|
|
14