Fig. 1 — Heat Section Details

NOTE: High heat consists of sections 1 and 2. Low heat consists of section 1 only.

030-050 SIZES

NOTE: High heat consists of sections 1-3. Low heat consists of sections 1 and 2 only.

055-105 SIZES

Fig. 1 — Heat Section Details

10.Using the scrolling marquee, enable the unit to run using the following procedure:

a.Push the ESCAPE key unit a blank display screen is shown.

b.Push the Manual background key until the SERVICE TEST LED is lit.

c.Push the ENTER key. The display will show STOP.

d.Push the ENTER key again. The NO/YES display will flash.

e.Push the Manual backgroundManual backgroundManual background or Manual background key to toggle the display to NO

and then push ENTER . The unit will return to

normal operation and exit SERVICE TEST mode.

11.To test the operation of the gas section, use the scrolling marquee Service Test routine to energize the gas outputs and to turn on the gas. Refer to the unit Controls, Start- Up, Operation, Service and Troubleshooting literature for more information.

12.For normal operation, make sure that units with a conven- tional thermostat are set to heating control temperature. On VAV (variable air volume) and constant volume units with a space temperature sensor, make sure that the set points are at the normal heat set points.

If the main burners fail to light, or the blower fails to come on, shut down gas heating section and call your dealer for service. Failure to follow these requirements could result in serious personal injury.