CFM AFK-27 manual PRODUCT SPECIFICATION GUIDE 1.0 GENERAL, Fan Housing, Fan Impeller, Fan Testing

Models: AFK-12 AFK-0906 AFK-16 AFK-32 AFK-24 AFK-36 AFK-30 AFK-18 AFK-21 AFK-42 AFK-14 AFK-27

1 4
Download 4 pages 14.7 Kb
Page 3
Image 3

AFK FLANGE FAN

PRODUCT SPECIFICATION GUIDE

1.0GENERAL

A.Fans shall be model AFK Flange Fans, as manufactured by Continental Fan Manufacturing Inc., of Buffalo, NY, and of the size, capacity and flow direction as indicated on the drawings and fan schedule.

B.Fans shall be rated and tested in accordance with ANSI/AMCA Standard 210-99.

C.All motors and electrical components shall conform to NEMA standards.

2.0FAN HOUSING

A.Fan housing shall be constructed of rolled and continuously welded heavy gauge steel.

B.Inlet and outlet flanges shall be integrally formed to ensure concentricity and alignment of the flanges.

C.Adjustable motor base shall be constructed from heavy gauge steel and bolted to the flange.

D.Fan housing and motor base shall be coated with baked polyester powder coat finish.

3.0FAN IMPELLER

A.Axial impeller shall be constructed of spark resistant die cast aluminum airfoil shaped blades secured to a die cast aluminum hub assembly.

B.Axial impeller blades shall be of adjustable pitch construction with multiple hub-to-blade arrangements to maximize air performance. Blade pitch angles shall be factory set.

C.Axial impeller hub shall be designed to incorporate a split taper bushing, and be keyed directly to drive shaft.

4.0FAN MOTOR AND DRIVE

A.Motor shall be TEFC industrial duty and conform to NEMA standards.

B.Motor shall be of voltage, horsepower, RPM and enclosure as indicated on the fan schedule.

5.0OPTIONAL FAN ACCESSORIES

A.Where indicated, fan shall be provided with the following optional accessories:

Mounting panel

AMCA spark resistant construction

Motor side guard

Reverse flow construction

Propeller side guard

Special materials

Special coatings

Housing yoke with mounting bracket

Motors

-Explosion proof

-Special duty

6.0FAN TESTING

A.Axial impeller shall be balanced and mounted in fan assembly.

B.Fan assembly shall be run and tested prior to shipment.

C.A test report shall be maintained on file for each individual fan.