Specifications
AC Input | |
Operating Temperature | 0º to 50º C (32º to 122º F) |
Storage Temperature | |
Cooling | Convection |
DC Output | 2.16 VPC for lead Acid, 1.45 VPC for nickel cadmium |
- Float | |
- Equalize | 2.33 VPC for lead Acid, 1.55 VPC for nickel cadmium |
Current Limit | Approximately 135% |
Enclosure | 304 stainless steel hinged cover to facilitate installation |
Model | D.C. Output | Height | Width | Depth | Approx. | |
Number | Amps | System | Inches | Inches | Inches | Weight |
Voltage | ||||||
|
| 12 Volt |
|
|
| |
AA1206* | 6 | 12 | 11 | 9 | 8.5 | 12 |
AA1210* | 10 | 12 | 11 | 9 | 8.5 | 14 |
AA1220* | 20 | 12 | 11 | 9 | 8.5 | 22 |
|
| 24 Volt |
|
|
| |
AA2406* | 6 | 24 | 11 | 9 | 8.5 | 14 |
AA2410* | 10 | 24 | 11 | 9 | 8.5 | 22 |
AA2420* | 20 | 24 | 13 | 16.5 | 8.5 | 38 |
|
| 32 Volt |
|
|
| |
AA3206 | 6 | 32 | 11 | 9 | 8.5 | 22 |
AA3210 | 10 | 32 | 11 | 9 | 8.5 | 26 |
VPC | Typical Output Curve |
2.5 |
|
2.4 | Equalize |
| |
2.3 |
|
2.2 | Float |
2.1 |
|
2.0
1.9
1.8
0 10 20 30 40 50 60 70 80 90 100
% OF RATED CHARGING CURRENT (AMPS)
*UL Listed
Optional Accessories
• | Remote summary relay | • Low DC voltage alarm relay | • | Combined Low/High voltage | |
• | Battery temperature | • | High DC voltage alarm relay |
| alarm relays |
| compensation | • | Current failure relay | • | AC power failure relay |
Ordering Information
When ordering, please specify:
1.Model number
2.AC input: voltage & frequency
3.Battery type and number of cells
4.
5.Recharge time desired
6.Description of load
7.Options
Contact your Charles sales representative for specific product information.
Charles Industries, Ltd. | Voice: | (847) |
|
IS0 9000 | |||
Industrial Group | Fax: | (847) | REGISTERED |
5600 Apollo Drive | QUALITY SYSTEM | ||
|
|
|
|
Rolling Meadows, IL 60008 USA