C.Inlet screen of Sump Pump is blocked, or Impeller is jammed. Remove Pump and clean the Impeller.

4.Pump Motor runs, but delivers small amount of water.

A.Vertical lift is approaching Sump Pump’s maximum lift capability. Maximum lift capability is 36 feet. Reduce height of vertical lift.

B.Inlet is partially blocked. Check to make sure inlet is clear of debris.

C.Discharge Hose is partially blocked. Check Hose for blockage.

5.Circuit breaker trips or fuse blows when Sump Pump starts.

A.Breaker or fuse size is too small. A minimum 15 AMP breaker or fuse should be used.

B.Other major appliances are on the same circuit. Sump Pump should be on its own separate circuit.

C.Sump Pump is connected to an extension cord, or wiring is inadequate. DO NOT USE EXTENSION CORDS. Have a qualified service technician check for proper wiring.

D.Defective Switch or Motor. Have a qualified service technician check Switch and Motor for proper operation.

INSPECTION, MAINTENANCE, AND CLEANING

1. WARNING! Always make sure the electrical power to the Sump Pump’s GFCI electrical outlet is shut off first and then the Pump is unplugged from its outlet prior to performing any inspection, maintenance, or cleaning to the unit.

2.Before each use, inspect the general condition of the Sump Pump. Check for clogs throughout the system, misalignment or binding of moving parts, damaged electrical wiring, damaged or loose discharge hoses, and any other condition that may affect its safe operation. If abnormal noise or vibration occurs, have the problem corrected before further use. Do not use damaged equipment.

3.If the Sump Pump is not in use due to dry conditions, etc., pour enough water into the pit to activate the Pump once every 3 months.

4.Periodically, check to make sure the pit is free from accumulated debris, rocks, and other objects that may damage the Sump Pump.

5.When cleaning, spray the exterior and Impeller of the Sump Pump with a garden hose. Do not introduce water or any other liquid into the Motor Housing.

6.In cold weather, when the Sump Pump is not in use, protect the interior of the Pump from freezing by draining the liquid and pumping a permanent type

automobile antifreeze containing a rust inhibitor through the system. A 50% mixture

SKU 92481

For technical questions, please call 1-800-444-3353.

PAGE 11

Page 11
Image 11
Chicago Electric 92481 manual INSPECTION, MAINTENANCE, and Cleaning, Pump Motor runs, but delivers small amount of water