Chromalox PF495-1 specifications General Information, Installation, Operation, January

Models: PF495-1

1 4
Download 4 pages 17.07 Kb
Page 1
Image 1
Installation, Operation

Installation, Operation

and

RENEWAL PARTS IDENTIFICATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Supersedes PF495)

PF495-1

161-304509-001

JANUARY, 2003

Industrial Wall Mounted Natural Convection

Space Heater - Type H

Specifications

Model

Output

Voltage

Output

Dimensions (In.)

Wt.

(kW)

(Vac)

(BTUH)

Width

Height

Depth

Lbs.

 

H-1801

1.0

120

2

20-3/4

7-1/2

4-1/2

28

H-1801

1.0

240

2

20-3/4

7-1/2

4-1/2

28

 

 

 

 

 

 

 

 

H-2405

1.5

120

2

26-1/2

7-1/2

4-1/2

30

H-2405

1.5

240

2

26-1/2

7-1/2

4-1/2

30

H-2405

1.5

480

2

26-1/2

7-1/2

4-1/2

30

 

 

 

 

 

 

 

 

H-2406

2.0

120

4

26-1/2

11-1/4

4-1/2

32

H-2406

2.0

240

4

26-1/2

11-1/4

4-1/2

32

H-2406

2.0

480

4

26-1/2

11-1/4

4-1/2

32

 

 

 

 

 

 

 

 

H-2407

3.0

240

4

26-1/2

11-1/4

4-1/2

32

H-2407

3.0

480

4

26-1/2

11-1/4

4-1/2

32

GENERAL INFORMATION

ELECTRIC SHOCK HAZARD. Disconnect all power before installing or servicing heater. Failure to do so could result in personal injury or property dam- age. Heater must be installed by a qualified person in accordance with the National Electrical Code, NFPA 70.

1.All wiring should be done in accordance with local codes and the National Electrical Code by a qualified person.

2.Connect air heaters to same line voltage as on heater nameplate.

3.Check possibility of corrosion if heaters are operated in atmos-

pheres other than air.

4. In general, locate heater approximately 1 foot from the floor, but not less than 6 inches, for best overall results. Heater, however, can be located anywhere to meet unique requirements of any particu- lar application.

5.Heaters are mounted directly on any type of noncombustible sur- face—masonry, concrete, block, plastered walls, metal framework, etc.— using appropriate hardware.

6.Standard heaters are mounted in a horizontal position with the ter- minal end on the left.

The system designer is responsible for the safety of this equipment and should install adequate back-up controls and safety devices with their electric heating equipment. Where the conse- quences of failure could result in personal injury or property damage, back-up controls are essential.