![Chromalox®](/images/new-backgrounds/43663/436631x1.webp)
Chromalox®
Installation, Operation
and
RENEWAL PARTS IDENTIFICATION
|
|
|
|
DIVISION 4 |
| SECTION DRA | |
SALES | (Supersedes(S des | ||
REFERENCE | |||
|
|
| |
DATE NOVEMBER, 2002 |
|
Portable Industrial
Unit Blower Air Heater
Type DRA
Specifications – Table 1
Model |
| Electrical Data (60 Hz) |
|
| Dimensions (In.) |
| |||
Volts | kW | Phase | Amps* 1/3 Ph | BTU | Height | Width | Depth | ||
| |||||||||
208 | 7.5 | 1 and 3 | 36.3/21.0 | 25,590 | 34.25 | 27.5 | 25 | ||
240/208 | 7.5/5.6 | 1 and 3 | 31.5/18.3** | 25,590 | 34.25 | 27.5 | 25 | ||
208 | 9.75 | 1 and 3 | 47.1/27.3 | 33,267 | 34.25 | 27.5 | 25 | ||
240/208 | 9.75/7.3 | 1 and 3 | 40.8/23.7** | 33,267 | 34.25 | 27.5 | 25 | ||
208 | 15 | 3 | 41.8 | 51,180 | 34.25 | 27.5 | 25 | ||
240/208 | 15/11.2 | 3 | 36.3** | 51,180 | 34.25 | 27.5 | 25 | ||
480 | 15 | 1 and 3 | 31.4/18.2 | 51,180 | 34.25 | 27.5 | 25 | ||
600 | 15 | 1 and 3 | 25.2/14.6 | 51,180 | 34.25 | 27.5 | 25 | ||
240/208 | 19.5/15 | 3 | 47.1** | 66,534 | 34.25 | 27.5 | 26.5 | ||
480 | 20 | 1 and 3 | 42.0/24.4 | 68,240 | 34.25 | 27.5 | 26.5 | ||
600 | 20 | 1 and 3 | 33.5/19.4 | 68,240 | 34.25 | 27.5 | 26.5 | ||
480 | 30 | 3 | 36.3 | 102,360 | 34.25 | 27.5 | 26.5 | ||
600 | 30 | 3 | 20.1 | 102,360 | 34.25 | 27.5 | 26.5 | ||
|
|
|
|
|
|
|
|
|
*= Includes motor amps
**= Ratings shown are for 240V, 208V amperage is 86% of 240V value.
Models shown as 1 and 3 phase are factory wired for 3 phase operation and can be field wired for single phase.
GENERAL
IMPORTANT:
SAVE THESE INSTRUCTIONSRisk of fire. Do not use as a residential or house- hold heater.
Hazard of Fire or Discoloration of Temperature Sensitive Fabrics. Do not use as a residential or household heater. Keep combustible material and
such fabrics away from heater. Do not operate heater where flammable vapors, gases or liquids are present. Heaters in the heat mode should not be operated in room temperatures above 80°F. Fan motor is not designed to operate in ambients below
To avoid personal injury read “IMPORTANT INSTRUCTIONS” on page 2 before installation or operation of heater.
Keep electrical cords and combustible materials, such as drapes and other furnishings, away from heater.
© 2010 Chromalox, Inc.