CONTACTOR FAILS TO ENERGIZE
If the contactor fails to energize, check for blown fuses in the control circuit. If the fuses are not blown, check the contac- tor holding coil. The holding coil can be checked by jumpering Terminal L1 of the line and Terminal No. 4 (coil lead) on the contactor. See Figure 1.
A. If the contactor fails to energize, then the coil is defective. B. If the contactor energizes, it is an indication of failure in either the Pressure Control or in the
wire mercury switch.
Figure 1
Since the Pressure Control and the three wire mercury switch are wired in series, they can be checked one at a time by placing a jumper across each control. If the mercury switch or Pressure Control fail to energize, check the
At this point, the contactor should energize unless there is an open wire in the control circuit.
PRESSURE CONTROL — Malfunctions in the pressure control can be mechanical or electrical.
The bellows should be removed and the small orifice at the bottom cleaned out. The bellows must be replaced if it is punc- tured. The syphon tubing should also be cleaned by steam while the control is removed; it will be necessary to join the two loose leads in order to activate the boiler. See Figure 3.
The electrical controls should be checked by referring to the Contactors, Elements and Voltages section.
NOTE: If control is purchased locally, remove
Figure 2 — Low Water
Pressure |
|
Control | Differential |
Setting | |
| Control |
| Setting |
Bellows
Syphon
Tube
Figure 3 — Pressure Control